EMR-4000
IM02602009E
Device Planning Parameters of the Trip Circuit Monitoring Module
Parameter
Description
Options
Default
Menu path
Mode
Mode
Do not use,
Use
Use
[Device Planning]
Global Protection Parameters of the Trip Circuit Monitoring Module
Parameter
Description
Setting range
Default
Menu path
Mode
Select if trip circuit is going to be monitored when the
breaker is closed or when the breaker is either open or
close.
Closed,
Either
Closed
[Protection Para
/Global Prot Para
/Supervision
/TCM]
Input 1
Select the input configured to monitor the trip coil when
the breaker is closed.
1..n, Dig Inputs
DI-8P X1.DI 1
[Protection Para
/Global Prot Para
/Supervision
/TCM]
Input 2
Select the input configured to monitor the trip coil when
the breaker is open. Only available if Mode set to
“Either”.
Only available if: Mode = Either
1..n, Dig Inputs
-.-
[Protection Para
/Global Prot Para
/Supervision
/TCM]
ExBlo1
External blocking of the module, if blocking is activated
(allowed) within a parameter set and if the state of the
assigned signal is true.
1..n, Assignment
List
-.-
[Protection Para
/Global Prot Para
/Supervision
/TCM]
ExBlo2
External blocking of the module, if blocking is activated
(allowed) within a parameter set and if the state of the
assigned signal is true.
1..n, Assignment
List
-.-
[Protection Para
/Global Prot Para
/Supervision
/TCM]
www.eaton.com
779
Содержание EMR-4000
Страница 61: ...EMR 4000 IM02602009E Ethernet RJ45 Terminal Marking www eaton com 61 1 8 TxD TxD RxD N C N C RxD N C N C...
Страница 423: ...EMR 4000 IM02602009E Name Description Logic LE23 Out inverted Signal Negated Latched Output Q NOT www eaton com 423...
Страница 493: ...EMR 4000 IM02602009E Motor Protection Curves Motor Protection Curve Example 1 www eaton com 493...
Страница 494: ...EMR 4000 IM02602009E Motor Protection Curve Example 2 without RTDs www eaton com 494...
Страница 495: ...EMR 4000 IM02602009E Motor Protection Curve Example 3 with RTDs www eaton com 495...