EMR-4000
IM02602009E
www.eaton.com
873
t [s]
t-multiplier
t =
29.1
*t-multiplier [s]
Pickup
-1
I
( )
2
Trip
Reset
x * Pickup
(Multiples of Pickup)
t =
28.2
*t-multiplier [s]
Pickup
-1
I
( )
2
+ 0.1217
( )
Notice!
Various Reset Modes are available . Resetting via characteristic, delayed, and
instantaneous .
ANSI EINV