EMR-4000
IM02602009E
DI-8P X
Name of the Assembly group:
DI-8P X1
Device Parameters of the Digital Inputs on DI-8P X
Parameter
Description
Setting range
Default
Menu path
Nom Voltage
Nominal voltage of the digital inputs
24 V dc,
48 V dc,
60 V dc,
110/120 V dc,
230/240 V dc,
110/120 V ac,
230/240 V ac
110/120 V dc
[Device Para
/Digital Inputs
/DI-8P X1
/Group 1]
Inverting 1
Inverting the input signals.
Inactive,
Active
Inactive
[Device Para
/Digital Inputs
/DI-8P X1
/Group 1]
Debouncing Time 1 A change of the state of a digital input will only be
recognized after the debouncing time has expired
(become effective). Thus, transient signals will not be
misinterpreted.
No Debouncing
Time,
20 ms,
50 ms,
100 ms
20 ms
[Device Para
/Digital Inputs
/DI-8P X1
/Group 1]
Nom Voltage
Nominal voltage of the digital inputs
24 V dc,
48 V dc,
60 V dc,
110/120 V dc,
230/240 V dc,
110/120 V ac,
230/240 V ac
110/120 V dc
[Device Para
/Digital Inputs
/DI-8P X1
/Group 2]
Inverting 2
Inverting the input signals.
Inactive,
Active
Inactive
[Device Para
/Digital Inputs
/DI-8P X1
/Group 2]
www.eaton.com
76
Содержание EMR-4000
Страница 61: ...EMR 4000 IM02602009E Ethernet RJ45 Terminal Marking www eaton com 61 1 8 TxD TxD RxD N C N C RxD N C N C...
Страница 423: ...EMR 4000 IM02602009E Name Description Logic LE23 Out inverted Signal Negated Latched Output Q NOT www eaton com 423...
Страница 493: ...EMR 4000 IM02602009E Motor Protection Curves Motor Protection Curve Example 1 www eaton com 493...
Страница 494: ...EMR 4000 IM02602009E Motor Protection Curve Example 2 without RTDs www eaton com 494...
Страница 495: ...EMR 4000 IM02602009E Motor Protection Curve Example 3 with RTDs www eaton com 495...