EMR-4000
IM02602009E
Parameter
Description
Setting range
Default
Menu path
LB Alarm
Load Bearing Threshold for Temperature Alarm
Only available if: Device Planning: Alarm Function = Use
0 - 200°C
80°C
[Protection Para
/<1..4>
/Temp-Prot
/RTD
/LB Group]
LB t-Delay
Load Bearing If this time is expired a Temperature Alarm
will be generated.
Only available if: Device Planning: Alarm Function = Use
0 - 360min
1min
[Protection Para
/<1..4>
/Temp-Prot
/RTD
/LB Group]
LB Trip
Load Bearing Threshold for Temperature Trip
Only available if: Device Planning: Trip Function = Use
0 - 200°C
80°C
[Protection Para
/<1..4>
/Temp-Prot
/RTD
/LB Group]
Aux Alarm Function Auxiliary Alarm Function
Inactive,
Active
Inactive
[Protection Para
/<1..4>
/Temp-Prot
/RTD
/Aux Group]
Aux Trip Function
Auxiliary Trip Function
Inactive,
Active
Inactive
[Protection Para
/<1..4>
/Temp-Prot
/RTD
/Aux Group]
Aux Alarm
Auxiliary Threshold for Temperature Alarm
Only available if: Device Planning: Alarm Function = Use
0 - 200°C
80°C
[Protection Para
/<1..4>
/Temp-Prot
/RTD
/Aux Group]
Aux t-Delay
Auxiliary If this time is expired a Temperature Alarm will
be generated.
Only available if: Device Planning: Alarm Function = Use
0 - 360min
1min
[Protection Para
/<1..4>
/Temp-Prot
/RTD
/Aux Group]
www.eaton.com
716
Содержание EMR-4000
Страница 61: ...EMR 4000 IM02602009E Ethernet RJ45 Terminal Marking www eaton com 61 1 8 TxD TxD RxD N C N C RxD N C N C...
Страница 423: ...EMR 4000 IM02602009E Name Description Logic LE23 Out inverted Signal Negated Latched Output Q NOT www eaton com 423...
Страница 493: ...EMR 4000 IM02602009E Motor Protection Curves Motor Protection Curve Example 1 www eaton com 493...
Страница 494: ...EMR 4000 IM02602009E Motor Protection Curve Example 2 without RTDs www eaton com 494...
Страница 495: ...EMR 4000 IM02602009E Motor Protection Curve Example 3 with RTDs www eaton com 495...