EMR-4000
IM02602009E
Disarming the Relay Output Contacts
The parameters, their defaults, and setting ranges have to be taken from
the Relay Output Contacts section.
Principle – General Use
Within this mode [Service/Test Mode (Prot inhibit)/WARNING! Cont?/DISARMED], entire groups of relay output
contacts can be disabled.
By means of this test mode, contact outputs switching actions of the relay output contacts
are prevented.
If the relay output contacts are disarmed, maintenance actions can be carried out without the risk of
taking entire processes off-line.
The User MUST ENSURE that the relay output contacts are ARMED AGAIN
after maintenance is complete.
If they are not armed, the protective device
WILL NOT provide protection.
Zone Interlocking Output and the Supervision Contact cannot be disarmed.
Within this mode [Service/Test Mode (Prot inhibit)/WARNING! Cont?/DISARMED] entire groups of relay output contacts
can be disarmed:
Permanent; or
Via timeout.
If they are set with a timeout, they will keep their “Disarm Position” only as long as this timer runs.
If the timer
expires,
the relay output contacts will operate normally.
If they are set Permanent, they will keep the “Disarm State”
continuously.
www.eaton.com
806
Содержание EMR-4000
Страница 61: ...EMR 4000 IM02602009E Ethernet RJ45 Terminal Marking www eaton com 61 1 8 TxD TxD RxD N C N C RxD N C N C...
Страница 423: ...EMR 4000 IM02602009E Name Description Logic LE23 Out inverted Signal Negated Latched Output Q NOT www eaton com 423...
Страница 493: ...EMR 4000 IM02602009E Motor Protection Curves Motor Protection Curve Example 1 www eaton com 493...
Страница 494: ...EMR 4000 IM02602009E Motor Protection Curve Example 2 without RTDs www eaton com 494...
Страница 495: ...EMR 4000 IM02602009E Motor Protection Curve Example 3 with RTDs www eaton com 495...