EMR-4000
IM02602009E
Global Protection Parameters of the Analog Outputs
Parameter
Description
Setting range
Default
Menu path
Assignment
Assignment
1..n,
AnalogOutputList
-.-
[Device Para
/Analog Outputs
/AnOut[1]]
Range
Adjustable range
0...20mA,
4...20mA,
0...10V
0...20mA
[Device Para
/Analog Outputs
/AnOut[1]]
Range max
Adjustable range maximum.
-999999.00 -
999999.00°C
1.00°C
[Device Para
/Analog Outputs
/AnOut[1]]
Range min
Adjustable range minimum.
-999999.00 -
999999.00°C
0.00°C
[Device Para
/Analog Outputs
/AnOut[1]]
Force Mode
For commissioning purposes or for maintanance, Analog
Outputs can be set by force. By means of this function
the normal Analog Outputs can be overwritten (forced).
Permanent,
Timeout
Permanent
[Service
/Test Mode (Prot
inhibit)
/WARNING! Cont?
/Analog Outputs
/AnOut[1]]
t-Timeout Force
The Analog Output Value will be set by force for the
duration of this time. That means for the duration of this
time the Analog Output does not show the value of the
signals that are assigned on it.
Only available if: Force Mode = Active
0.00 - 300.00s
0.03s
[Service
/Test Mode (Prot
inhibit)
/WARNING! Cont?
/Analog Outputs
/AnOut[1]]
www.eaton.com
128
Содержание EMR-4000
Страница 61: ...EMR 4000 IM02602009E Ethernet RJ45 Terminal Marking www eaton com 61 1 8 TxD TxD RxD N C N C RxD N C N C...
Страница 423: ...EMR 4000 IM02602009E Name Description Logic LE23 Out inverted Signal Negated Latched Output Q NOT www eaton com 423...
Страница 493: ...EMR 4000 IM02602009E Motor Protection Curves Motor Protection Curve Example 1 www eaton com 493...
Страница 494: ...EMR 4000 IM02602009E Motor Protection Curve Example 2 without RTDs www eaton com 494...
Страница 495: ...EMR 4000 IM02602009E Motor Protection Curve Example 3 with RTDs www eaton com 495...