background image

HOKKIM DIGITAL AUTOMATIC MAINS FAILURE CONTROLLER MANUAL FOR MODEL 
DAMF-5.

INTRODUCTION

Thank you for purchasing the Hokkim Digital Automatic Mains Failure Controller model; DAMF-

5.  We will do our utmost  to provide you with the best service in terms of technical support, stock and 
parts replacement. This manual should be read through before attempting to install the unit in order to 
avoid damage due to wrong connections. You need to be familiar with this manual in order to fully 
understand the functions and features the DAMF-5 can provide for you. A copy should be handed to the 
owner’s maintenance team for future reference with a briefing on how to operate it.

The design and development of the Hokkim Digital DAMF-5 Controller comes from many years 

of studying the traditional 

AMF

 boards hard wired with relays and timers. The heart of the DAMF-5  is 

Micro Controller based. It is very flexible, compact, easy to use and comes with many features to suit 
most  

AMF

  needs.   Due   to   our   policy   of   continuous   development,   we   welcome   suggestions   for 

improvements. Thus, there may be changes after this manual is produced. If in doubt, do not hesitate to 
call for our technical support or information on our latest models.

PARTS IDENTIFICATION

We are briefly going through the physical markings of the DAMF-5 so that you can easily locate them 
when needed.

1. Front Face Diagram 1.

 

  Refer to page 4. It shows the front face of the DAMF-5. There are 6 nos. red 

LED to indicate; 1) STARTER. 2) RUN. 3) FUEL SOLENOID. 4) ENERGIZED STOP. 5) 24V. 
and 6) 12V. During operation, these LEDs give a quick indications of what the DAMF-5 is doing.
Next is the 3 digit 7-segment display. This display is the most important interface as you will 
receive a host of information from it. To help you understand, we have provided the 3 digit 
abbreviations   at   the   front   face   for   easy  reference.   You   need   to   familiarize   yourself   with   the 
abbreviations as during operation, the display flashes at half second rate, you have to be quick to 
catch what function the DAMF-5 is performing.

2) Terminal Diagram 2

 

 . Refer to page 5. It shows the back terminals from T01 to T24 with the terminal 

abbreviations. Note that some of the abbreviations are the same beside different terminal number. 
This is the part where you have to be careful during connection. The top row of terminals T01 to 
T08 has a mixture of inputs, outputs, and auxiliary supply inputs. Beside T08 is marked 12V or 
24V,   you   can   connect   an   auxiliary   supply   of   12VDC   or   24VDC   and   the   DAMF-5   will 
automatically   switches   to   the   correct   voltage.   The   front   face   LED   voltage   indicator   should 
correspond with the auxiliary supply connected. The middle row of terminals T09 to T16 is clearly 
marked INPUTS. This is where you terminate the inputs from selector switches or alarm contacts. 
The   bottom   row   of   terminals   T17   to   T24   is   clearly  marked   OUTPUTS.   This   is   where   you 
terminate the outputs to relays or lamps. Lastly, at the bottom right is a tiny button marked SET. 
This button allows you to change default settings of the DAMF-5.

3) Terminal Abbreviations Diagram 3.

 

  Refer to page 7. On one side of the DAMF-5 is the Abbreviations 

For   Terminals   sticker.   It   shows   what   you   are   suppose   to   connect   to   each   terminal.   After 
familiarizing yourself with it, it speeds up connection work as you don't need to keep referring to 
the Connection Diagram 5.

Page 1 of 12

HOKKIM

giving you control

Control & Protection Relays

Содержание DAMF-5

Страница 1: ...is doing Next is the 3 digit 7 segment display This display is the most important interface as you will receive a host of information from it To help you understand we have provided the 3 digit abbreviations at the front face for easy reference You need to familiarize yourself with the abbreviations as during operation the display flashes at half second rate you have to be quick to catch what func...

Страница 2: ...e open to feed diesel to the engine 4 ENERGIZE STOP To stop the gen set the ESR relay energize this LED lights and fuel is cut from the engine Note gen sets use either Fuel Solenoid or Energize Stop 5 24V When auxiliary supply is 20VDC and above this LED lights Maximum allowable voltage is 32VDC 6 12V When auxiliary supply is 15VDC and below this LED lights Minimum allowable voltage is 7VDC IMPORT...

Страница 3: ...d Alarm bell sound and Low Fuel Level fault lamp flashes Alarm can be accepted 9 LOP Low Oil Pressure This display shows low oil pressure alarm has occur and gen set stopped and cannot be started After ESt count down press the MFB once to accept the alarm After clearing the fault press the MFB again to reset the alarm 10 LPt Lamp Test This display shows lamp test is being perform All alarm fault l...

Страница 4: ...he next parameter 10 seconds of inactivity and the new value will be burn into the memory The display is shown when this is taking place In case auxiliary supply failure occurs in this stage the memory burning may not be complete and you may have to repeat the process 19 SFC Supply Fail Contact If the supply fail contact setting is 1 then the supply fail timer start when supply fail contacts close...

Страница 5: ... mains supply fail the contacts close or open to start the gen set T05 GRR Generator Run Relay input from free contacts to negative When gen set has started its output voltage energizes this relay to close the contacts and stop the starter cranking Other wise also known as AFR AC Fail Relay T06 MFB Multi Function Button input from free contacts to negative This button is indeed used for many funct...

Страница 6: ...Low Oil Pressure alarm output to lamp Type open collector to negative Flashes when Low Oil Pressure fault occurs T22 HWT High Water Temperature alarm output to lamp Type open collector to negative Flashes when High Water Temperature fault occurs T23 OSP Over Speed alarm output to lamp Type open collector to negative Flashes when Over Speed fault occurs T24 LFL Low Fuel Level alarm output to lamp T...

Страница 7: ...minal Abbreviations Default Settings Diagram 3 Diagram 4 Note Lamp Test can only be performed in the Aut Mode Terminal Connection Diagram 5 Page 7 of 12 HOKKIM giving you control Control Protection Relays ...

Страница 8: ...ff and the Energize Stop LED lighted If in use check that the Energize Stop relay energizes Wait for about 45 seconds until the LED goes off and the relay de energizes All other relays or lamps should be off but the supply LED remain lighted This confirms the Emergency Stop is functioning Reset the button to continue 4 View Default Settings Remain in the Off mode press and release the MFB button t...

Страница 9: ... and rSt count down The Crt count down and rSt count down is repeated 6 times before Fail To Start alarm is triggered Notice the followings before the alarm is triggered the Fuel Solenoid LED is lighted FSR relay is energized when Crt count down begins the Starter LED is lighted and STR relay energizes when rSt count down begins the Starter LED is off and STR relay de energizes Once the alarm is t...

Страница 10: ...rt alarm will be triggered After the GRR input T05 touches negative the display shows OPt count down and when finished displays run to indicate gen set is running Remember to note the usual when Crt count down begins the Fuel Solenoid Relay and Starter Relay energizes when rSt count down begins Fuel Solenoid Relay remain energized while Starter Relay de energizes 13 Test Stop The test stop is the ...

Страница 11: ...r outputs are not shorted to positive of auxiliary supply 6 Make sure the alarm inputs resistance to negative is less then 500 ohms Higher resistance and the faults may not be triggered 7 Should alarm inputs give problem disconnect the wire from the DAMF 5 and test directly with jumper wire to negative 8 Do not connect power source to the inputs voltage higher then 12VAC will cause the internal fu...

Страница 12: ...Contact selectable close 1 or open 0 to start Standard 5 nos fault alarms Expandable fault alarms using external annunciator to External Fault Alarm input First Fault Alarm new faults differentiated from old Alarm cancel does not cancel siren from next fault Master Alarm Relay output MAR for Building Automation system BAS etc New Hokkim JKM terminals for easier connections Easy wiring reduces labo...

Отзывы: