Refer to Terminal Diagram 2. These terminals allows you to wired up the DAMF-5 to external relays, 
push buttons, selector switch, bell, fault inputs, lamps,  etc. to complete  the  

AMF

  Control Board. A 

detailed description of the terminals is given below;

Terminal 

Diagram 2

TERMINALS T01 TO T24

No.

Abbrev.

Details.

T01

0V

Negative

 of auxiliary supply.

T02

ESR

E

nergized 

S

top 

R

elay output to relay coil. Type; open collector to negative. 

The relay energize to stop the gen-set.

T03

FSR

F

uel 

S

olenoid 

R

elay output to relay coil. Type; open collector to negative. 

The relay energize to run the gen-set.

T04

SFC

S

upply 

F

ail 

C

ontact input from free contacts to negative. When mains supply 

fail, the contacts close or open to start the gen-set.

T05

GRR

G

enerator 

R

un 

R

elay input from free contacts to negative.When gen-set has 

started, its output voltage energizes this relay to close the contacts and stop 
the starter cranking. Other wise also known as 

AFR,

 AC Fail Relay.   

T06

MFB

M

ulti 

F

unction 

B

utton input from free contacts to negative.This button is 

indeed used for many functions. In fact it is the only button use to perform 
most required functions other then the Emergency Stop Button.

T07

ESB

E

mergency 

S

top 

B

utton input from free contacts to negative. When this 

button is pressed, the auxiliary supply is cut from the Micro Controller. All 
outputs ceases to operate except the Energized Stop Relay which energizes 
for approximately 45 seconds before releasing.

Page 5 of 12

HOKKIM

giving you control

Control & Protection Relays

Содержание DAMF-5

Страница 1: ...is doing Next is the 3 digit 7 segment display This display is the most important interface as you will receive a host of information from it To help you understand we have provided the 3 digit abbreviations at the front face for easy reference You need to familiarize yourself with the abbreviations as during operation the display flashes at half second rate you have to be quick to catch what func...

Страница 2: ...e open to feed diesel to the engine 4 ENERGIZE STOP To stop the gen set the ESR relay energize this LED lights and fuel is cut from the engine Note gen sets use either Fuel Solenoid or Energize Stop 5 24V When auxiliary supply is 20VDC and above this LED lights Maximum allowable voltage is 32VDC 6 12V When auxiliary supply is 15VDC and below this LED lights Minimum allowable voltage is 7VDC IMPORT...

Страница 3: ...d Alarm bell sound and Low Fuel Level fault lamp flashes Alarm can be accepted 9 LOP Low Oil Pressure This display shows low oil pressure alarm has occur and gen set stopped and cannot be started After ESt count down press the MFB once to accept the alarm After clearing the fault press the MFB again to reset the alarm 10 LPt Lamp Test This display shows lamp test is being perform All alarm fault l...

Страница 4: ...he next parameter 10 seconds of inactivity and the new value will be burn into the memory The display is shown when this is taking place In case auxiliary supply failure occurs in this stage the memory burning may not be complete and you may have to repeat the process 19 SFC Supply Fail Contact If the supply fail contact setting is 1 then the supply fail timer start when supply fail contacts close...

Страница 5: ... mains supply fail the contacts close or open to start the gen set T05 GRR Generator Run Relay input from free contacts to negative When gen set has started its output voltage energizes this relay to close the contacts and stop the starter cranking Other wise also known as AFR AC Fail Relay T06 MFB Multi Function Button input from free contacts to negative This button is indeed used for many funct...

Страница 6: ...Low Oil Pressure alarm output to lamp Type open collector to negative Flashes when Low Oil Pressure fault occurs T22 HWT High Water Temperature alarm output to lamp Type open collector to negative Flashes when High Water Temperature fault occurs T23 OSP Over Speed alarm output to lamp Type open collector to negative Flashes when Over Speed fault occurs T24 LFL Low Fuel Level alarm output to lamp T...

Страница 7: ...minal Abbreviations Default Settings Diagram 3 Diagram 4 Note Lamp Test can only be performed in the Aut Mode Terminal Connection Diagram 5 Page 7 of 12 HOKKIM giving you control Control Protection Relays ...

Страница 8: ...ff and the Energize Stop LED lighted If in use check that the Energize Stop relay energizes Wait for about 45 seconds until the LED goes off and the relay de energizes All other relays or lamps should be off but the supply LED remain lighted This confirms the Emergency Stop is functioning Reset the button to continue 4 View Default Settings Remain in the Off mode press and release the MFB button t...

Страница 9: ... and rSt count down The Crt count down and rSt count down is repeated 6 times before Fail To Start alarm is triggered Notice the followings before the alarm is triggered the Fuel Solenoid LED is lighted FSR relay is energized when Crt count down begins the Starter LED is lighted and STR relay energizes when rSt count down begins the Starter LED is off and STR relay de energizes Once the alarm is t...

Страница 10: ...rt alarm will be triggered After the GRR input T05 touches negative the display shows OPt count down and when finished displays run to indicate gen set is running Remember to note the usual when Crt count down begins the Fuel Solenoid Relay and Starter Relay energizes when rSt count down begins Fuel Solenoid Relay remain energized while Starter Relay de energizes 13 Test Stop The test stop is the ...

Страница 11: ...r outputs are not shorted to positive of auxiliary supply 6 Make sure the alarm inputs resistance to negative is less then 500 ohms Higher resistance and the faults may not be triggered 7 Should alarm inputs give problem disconnect the wire from the DAMF 5 and test directly with jumper wire to negative 8 Do not connect power source to the inputs voltage higher then 12VAC will cause the internal fu...

Страница 12: ...Contact selectable close 1 or open 0 to start Standard 5 nos fault alarms Expandable fault alarms using external annunciator to External Fault Alarm input First Fault Alarm new faults differentiated from old Alarm cancel does not cancel siren from next fault Master Alarm Relay output MAR for Building Automation system BAS etc New Hokkim JKM terminals for easier connections Easy wiring reduces labo...

Отзывы: