Abbrev.

Details.

T08

+V

Positive

 of auxiliary supply. 12VDC or 24VDC.

T09

AUT

Aut

omatic mode input from free contacts to negative.

T10

MAN

Man

ual mode input from free contacts to negative.

T11

TES

Tes

t mode input from free contacts to negative.

T12

EFA

E

xternal 

F

ault 

A

larm input from free contacts to negative.When 

additional faults are required, an external alarm annunciator is added to 
provide the contacts to shutdown the gen-set when external faults occurs.

T13

LOP

L

ow 

O

il 

P

ressure alarm input from free contacts to negative.

T14

HWT

H

igh 

W

ater 

T

emperature alarm input from free contact to negative.

T15

OSP

O

ver 

Sp

eed alarm input from free contacts to negative.

T16

LFL

L

ow 

F

uel 

L

evel alarm input from free contacts to negative.

T17

STR

St

arter 

R

elay output to relay coil. Type; open collector to negative. This 

relay energize to crank the gen-set starter.

T18

BEL

Bel

l output to alarm bell coil. Type; open collector to negative. The bell 

sound when fault occurs.

T19

MAR

M

aster 

A

larm 

R

elay output to relay coil. Type; open collector to 

negative. This relay energizes when any fault occurs. It is use for remote 
signaling or 

BAS

 Building Automation System.

T20

FTS

F

ail 

T

S

tart alarm output to lamp. Type; open collector to negative. 

Flashes when Fail To Start fault occurs.

T21

LOP

L

ow 

O

il 

P

ressure alarm output to lamp. Type; open collector to negative. 

Flashes when Low Oil Pressure fault occurs.

T22

HWT

H

igh 

W

ater 

T

emperature alarm output to lamp. Type; open collector to 

negative. Flashes when High Water Temperature fault occurs.

T23

OSP

O

ver 

Sp

eed alarm output to lamp. Type; open collector to negative. 

Flashes when Over Speed fault occurs.

T24

LFL

L

ow 

F

uel 

L

evel alarm output to lamp. Type; open collector to negative. 

Flashes when Low Fuel Level fault occurs.

-

  SET

Set

 button to allow changing of default factory settings of a range of 

parameters to suit your requirements. Operates only in 

OFF

 mode.

INSTALLATION AND WIRING

The DAMF-5 is 96 x 96 DIN size front panel mounted. After fixing it together with all related items, 
commence   wiring   by  referring   to   diagram   5.   If  possible,   mark   the   wires   according   to   the   terminal 
numbers. This allows for easier trouble shooting. Some of the terminations will not be required as the unit 
allows for various possibilities. Use a 6A fuse or  

MCB

  (Miniature Circuit Breaker) for the DAMF-5 

auxiliary supply to protect against accidental shorting. A separate 20A fuse or 

MCB

 for fuel solenoid and 

starter supply. Note that the 

GRR

 relay coil must be 240VAC and the supply taken from incoming side of 

main 

MCCB

 (Molded Case Circuit Breaker). Only one 

R1

 relay is use, for either Energized Stop or Fuel 

Solenoid. So, connect to either T02 or T03, which ever suit the gen-set.

Page 6 of 12

HOKKIM

giving you control

Control & Protection Relays

Содержание DAMF-5

Страница 1: ...is doing Next is the 3 digit 7 segment display This display is the most important interface as you will receive a host of information from it To help you understand we have provided the 3 digit abbreviations at the front face for easy reference You need to familiarize yourself with the abbreviations as during operation the display flashes at half second rate you have to be quick to catch what func...

Страница 2: ...e open to feed diesel to the engine 4 ENERGIZE STOP To stop the gen set the ESR relay energize this LED lights and fuel is cut from the engine Note gen sets use either Fuel Solenoid or Energize Stop 5 24V When auxiliary supply is 20VDC and above this LED lights Maximum allowable voltage is 32VDC 6 12V When auxiliary supply is 15VDC and below this LED lights Minimum allowable voltage is 7VDC IMPORT...

Страница 3: ...d Alarm bell sound and Low Fuel Level fault lamp flashes Alarm can be accepted 9 LOP Low Oil Pressure This display shows low oil pressure alarm has occur and gen set stopped and cannot be started After ESt count down press the MFB once to accept the alarm After clearing the fault press the MFB again to reset the alarm 10 LPt Lamp Test This display shows lamp test is being perform All alarm fault l...

Страница 4: ...he next parameter 10 seconds of inactivity and the new value will be burn into the memory The display is shown when this is taking place In case auxiliary supply failure occurs in this stage the memory burning may not be complete and you may have to repeat the process 19 SFC Supply Fail Contact If the supply fail contact setting is 1 then the supply fail timer start when supply fail contacts close...

Страница 5: ... mains supply fail the contacts close or open to start the gen set T05 GRR Generator Run Relay input from free contacts to negative When gen set has started its output voltage energizes this relay to close the contacts and stop the starter cranking Other wise also known as AFR AC Fail Relay T06 MFB Multi Function Button input from free contacts to negative This button is indeed used for many funct...

Страница 6: ...Low Oil Pressure alarm output to lamp Type open collector to negative Flashes when Low Oil Pressure fault occurs T22 HWT High Water Temperature alarm output to lamp Type open collector to negative Flashes when High Water Temperature fault occurs T23 OSP Over Speed alarm output to lamp Type open collector to negative Flashes when Over Speed fault occurs T24 LFL Low Fuel Level alarm output to lamp T...

Страница 7: ...minal Abbreviations Default Settings Diagram 3 Diagram 4 Note Lamp Test can only be performed in the Aut Mode Terminal Connection Diagram 5 Page 7 of 12 HOKKIM giving you control Control Protection Relays ...

Страница 8: ...ff and the Energize Stop LED lighted If in use check that the Energize Stop relay energizes Wait for about 45 seconds until the LED goes off and the relay de energizes All other relays or lamps should be off but the supply LED remain lighted This confirms the Emergency Stop is functioning Reset the button to continue 4 View Default Settings Remain in the Off mode press and release the MFB button t...

Страница 9: ... and rSt count down The Crt count down and rSt count down is repeated 6 times before Fail To Start alarm is triggered Notice the followings before the alarm is triggered the Fuel Solenoid LED is lighted FSR relay is energized when Crt count down begins the Starter LED is lighted and STR relay energizes when rSt count down begins the Starter LED is off and STR relay de energizes Once the alarm is t...

Страница 10: ...rt alarm will be triggered After the GRR input T05 touches negative the display shows OPt count down and when finished displays run to indicate gen set is running Remember to note the usual when Crt count down begins the Fuel Solenoid Relay and Starter Relay energizes when rSt count down begins Fuel Solenoid Relay remain energized while Starter Relay de energizes 13 Test Stop The test stop is the ...

Страница 11: ...r outputs are not shorted to positive of auxiliary supply 6 Make sure the alarm inputs resistance to negative is less then 500 ohms Higher resistance and the faults may not be triggered 7 Should alarm inputs give problem disconnect the wire from the DAMF 5 and test directly with jumper wire to negative 8 Do not connect power source to the inputs voltage higher then 12VAC will cause the internal fu...

Страница 12: ...Contact selectable close 1 or open 0 to start Standard 5 nos fault alarms Expandable fault alarms using external annunciator to External Fault Alarm input First Fault Alarm new faults differentiated from old Alarm cancel does not cancel siren from next fault Master Alarm Relay output MAR for Building Automation system BAS etc New Hokkim JKM terminals for easier connections Easy wiring reduces labo...

Отзывы: