4) Default Settings Diagram 4.

 

  Refer to page 7. It shows how to change the default factory setting of a 

range of parameters. It is advisable to view first the setting to confirm which parameters needs to 
be changed. Press the 

SET

 button follow by the 

MFB

 button to effect the change. This function 

can only be performed in the 

OFF

 mode.

5) Terminal Connection Diagram 5.

 

  Refer to page 7. On the other side of the DAMF-5 is the Terminal 

Connection   Diagram.   Note   that   the   terminals   number   are   not   in   order,   so   be   careful   when 
connecting the wires. It is easier to separate out the inputs from the outputs when drawing the 
diagram. Always refer to the terminal number together with the abbreviation to avoid mistake.

6) Dimension Diagram 6.

 

  Refer to page 12. It shows the physical shape and dimensions of the DAMF-5. 

The body is made of heat resistant ABS plastic and the front face and terminal is made of high 
impact PC (Poly Carbonate).

FRONT FACE.

Refer to Front Face Diagram 1. The 6 nos. red LEDs indicates to you what the DAMF-5 is doing during 
operation. They are as follows;

1. STARTER-When the 

STR

 relay energize, this LED lights, and the starter should be cranking to start 

the gen-set.

2. RUN- When gen-set runs, its output voltage energizes the 

GRR

 relay, this LED lights and the starter 

should stop cranking.

3. FUEL SOLENOID- To begin starting, the 

FSR

 relay energize, this LED lights and fuel solenoid valve 

open to feed diesel to the engine.

4. ENERGIZE STOP- To stop the gen-set, the 

ESR

 relay energize, this LED lights and fuel is cut from 

the engine. Note; gen-sets use either Fuel Solenoid or Energize Stop.

5. 24V - When auxiliary supply is 20VDC and above, this LED lights. Maximum allowable voltage is 

32VDC.

6. 12V - When auxiliary supply is 15VDC and below, this LED lights. Minimum allowable voltage is 

7VDC.

IMPORTANT NOTE : THE AUXILIARY SUPPLY SHOULD NOT BE ALLOWED TO RISE FROM 
BELOW   15VDC   TO   BELOW   20VDC.   BUT,   MAY   FALL   FROM   ABOVE   20VDC   TO   ABOVE 
15VDC. If you do not understand this statement, contact our technical personnel. Other wise damage may 
occur to the DAMF-5.

You need to study the 3 digit 7-segment display abbreviation and familiarize yourself with it as it is the 
most   important   interactive   interface   of   the   DAMF-5.   The   display  tells   you   what   function   is   being 
performed. If there is a count down timer, the display flashes between the count down time and the 
abbreviation at half second rate. A total of 20 abbreviations is listed below in alphabetical order;
1.

Att

 Attempts - This display shows the number of

 

set attempts of crank and rest before fail 

to   start 

alarm

 

occurs. It can be set from 1 to 9 attempts in 1 attempt increments. Default is 6.

2.

Aut

 Automatic - This display shows the automatic mode being selected. In this mode press the 

MFB 

button to perform lamp test.

3.

Crt

 Crank Starter Timer - This display shows cranking timer has started. The timer can be 

set from 

1 to 20 seconds in 1 second increments. Default is 6 seconds.

Page 2 of 12

HOKKIM

giving you control

Control & Protection Relays

Содержание DAMF-5

Страница 1: ...is doing Next is the 3 digit 7 segment display This display is the most important interface as you will receive a host of information from it To help you understand we have provided the 3 digit abbreviations at the front face for easy reference You need to familiarize yourself with the abbreviations as during operation the display flashes at half second rate you have to be quick to catch what func...

Страница 2: ...e open to feed diesel to the engine 4 ENERGIZE STOP To stop the gen set the ESR relay energize this LED lights and fuel is cut from the engine Note gen sets use either Fuel Solenoid or Energize Stop 5 24V When auxiliary supply is 20VDC and above this LED lights Maximum allowable voltage is 32VDC 6 12V When auxiliary supply is 15VDC and below this LED lights Minimum allowable voltage is 7VDC IMPORT...

Страница 3: ...d Alarm bell sound and Low Fuel Level fault lamp flashes Alarm can be accepted 9 LOP Low Oil Pressure This display shows low oil pressure alarm has occur and gen set stopped and cannot be started After ESt count down press the MFB once to accept the alarm After clearing the fault press the MFB again to reset the alarm 10 LPt Lamp Test This display shows lamp test is being perform All alarm fault l...

Страница 4: ...he next parameter 10 seconds of inactivity and the new value will be burn into the memory The display is shown when this is taking place In case auxiliary supply failure occurs in this stage the memory burning may not be complete and you may have to repeat the process 19 SFC Supply Fail Contact If the supply fail contact setting is 1 then the supply fail timer start when supply fail contacts close...

Страница 5: ... mains supply fail the contacts close or open to start the gen set T05 GRR Generator Run Relay input from free contacts to negative When gen set has started its output voltage energizes this relay to close the contacts and stop the starter cranking Other wise also known as AFR AC Fail Relay T06 MFB Multi Function Button input from free contacts to negative This button is indeed used for many funct...

Страница 6: ...Low Oil Pressure alarm output to lamp Type open collector to negative Flashes when Low Oil Pressure fault occurs T22 HWT High Water Temperature alarm output to lamp Type open collector to negative Flashes when High Water Temperature fault occurs T23 OSP Over Speed alarm output to lamp Type open collector to negative Flashes when Over Speed fault occurs T24 LFL Low Fuel Level alarm output to lamp T...

Страница 7: ...minal Abbreviations Default Settings Diagram 3 Diagram 4 Note Lamp Test can only be performed in the Aut Mode Terminal Connection Diagram 5 Page 7 of 12 HOKKIM giving you control Control Protection Relays ...

Страница 8: ...ff and the Energize Stop LED lighted If in use check that the Energize Stop relay energizes Wait for about 45 seconds until the LED goes off and the relay de energizes All other relays or lamps should be off but the supply LED remain lighted This confirms the Emergency Stop is functioning Reset the button to continue 4 View Default Settings Remain in the Off mode press and release the MFB button t...

Страница 9: ... and rSt count down The Crt count down and rSt count down is repeated 6 times before Fail To Start alarm is triggered Notice the followings before the alarm is triggered the Fuel Solenoid LED is lighted FSR relay is energized when Crt count down begins the Starter LED is lighted and STR relay energizes when rSt count down begins the Starter LED is off and STR relay de energizes Once the alarm is t...

Страница 10: ...rt alarm will be triggered After the GRR input T05 touches negative the display shows OPt count down and when finished displays run to indicate gen set is running Remember to note the usual when Crt count down begins the Fuel Solenoid Relay and Starter Relay energizes when rSt count down begins Fuel Solenoid Relay remain energized while Starter Relay de energizes 13 Test Stop The test stop is the ...

Страница 11: ...r outputs are not shorted to positive of auxiliary supply 6 Make sure the alarm inputs resistance to negative is less then 500 ohms Higher resistance and the faults may not be triggered 7 Should alarm inputs give problem disconnect the wire from the DAMF 5 and test directly with jumper wire to negative 8 Do not connect power source to the inputs voltage higher then 12VAC will cause the internal fu...

Страница 12: ...Contact selectable close 1 or open 0 to start Standard 5 nos fault alarms Expandable fault alarms using external annunciator to External Fault Alarm input First Fault Alarm new faults differentiated from old Alarm cancel does not cancel siren from next fault Master Alarm Relay output MAR for Building Automation system BAS etc New Hokkim JKM terminals for easier connections Easy wiring reduces labo...

Отзывы: