EMR-4000
IM02602009E
Configuration of the Voltage Based Average Value Calculation*
*=Availability depends on the ordered device code.
Voltage based Average Values
Time period for the
calculation of the
average values
Start options
Reset of the average and
peak values
Configuration Options
Where to configure?
In [Device Para\
Statistics\
Umit]
sliding:
(sliding: average calculation
based on sliding period)
fixed:
(fixed: Average calculation is
reset by the end of the period,
that means with the next starting
period)
duration:
(fixed or sliding period)
Start Fct:
(The average values are
calculated based on the time
period between two rising edges
ot this signal)
Res Fc
(e.g. via Digital Input in order to
reset the average values in
advance (before the next rising
edge of the start signal). This
applies to option »Start FC« only.
View average values
Where? Within menu [Operation\Statistics\Vavg]
Configuration of the Power Based Average Value Calculation*
*=Availability depends on the ordered device code.
Power based Average Values (Demand) and Peak Values
Time period for the
calculation of the
average and peak values
Start options
Reset of the average and
peak values
Configuration Options
Where to configure?
In [Device Para\
Statistics\
Bezugsmanagm\
Power Demand]
sliding:
(sliding: average calculation
based on sliding period)
fixed:
(fixed: Average calculation is
reset by the end of the period,
that means with the next starting
period)
duration:
(fixed or sliding period)
Start Fct:
(The average values are
calculated based on the time
period between two rising edges
ot this signal)
Res Fc
(e.g. via Digital Input in order to
reset the average values in
advance (before the next rising
edge of the start signal). This
applies to option »Start FC« only.
Trip (command) option to limit
the average power demand: Yes
Please refert to chapter »System Alarms«
View average values and peak
values
Where? Within menu [Operation\Statistics\Demand]
www.eaton.com
156
Содержание EMR-4000
Страница 61: ...EMR 4000 IM02602009E Ethernet RJ45 Terminal Marking www eaton com 61 1 8 TxD TxD RxD N C N C RxD N C N C...
Страница 423: ...EMR 4000 IM02602009E Name Description Logic LE23 Out inverted Signal Negated Latched Output Q NOT www eaton com 423...
Страница 493: ...EMR 4000 IM02602009E Motor Protection Curves Motor Protection Curve Example 1 www eaton com 493...
Страница 494: ...EMR 4000 IM02602009E Motor Protection Curve Example 2 without RTDs www eaton com 494...
Страница 495: ...EMR 4000 IM02602009E Motor Protection Curve Example 3 with RTDs www eaton com 495...