EMR-4000
IM02602009E
Parameter
Description
Setting range
Default
Menu path
Optical rest position Optical rest position
Light off,
Light on
Light on
[Device Para
/DNP
/Communication]
SelfAddress
Support of self (automatic) addresses
Inactive,
Active
Inactive
[Device Para
/DNP
/Communication]
DataLink confirm
Enables or disables the data layer confirmation (ack).
Never,
Always,
On_Large
Never
[Device Para
/DNP
/Communication]
t-DataLink confirm
Data layer confirmation timeout
0.1 - 10.0s
1s
[Device Para
/DNP
/Communication]
DataLink num
retries
Number of repetition of data link packet sending after
failing
0 - 255
3
[Device Para
/DNP
/Communication]
Direction Bit
Enables Direction Bit functionality. The Direction Bit is 0
for SlaveStation and 1 for MasterStation
Inactive,
Active
Inactive
[Device Para
/DNP
/Communication]
Max Frame Size
This value is used to limit the net Frame Size
64 - 255
255
[Device Para
/DNP
/Communication]
Test Link Period
This value specifies the time period when to send a Test
Link-Frame
0.0 - 120.0s
0s
[Device Para
/DNP
/Communication]
AppLink confirm
Determines if the device will request that the Application
Layer response be confirmed or not
Never,
Always,
Event
Always
[Device Para
/DNP
/Communication]
t-AppLink confirm
Application layer response timeout
0.1 - 10.0s
5s
[Device Para
/DNP
/Communication]
www.eaton.com
299
Содержание EMR-4000
Страница 61: ...EMR 4000 IM02602009E Ethernet RJ45 Terminal Marking www eaton com 61 1 8 TxD TxD RxD N C N C RxD N C N C...
Страница 423: ...EMR 4000 IM02602009E Name Description Logic LE23 Out inverted Signal Negated Latched Output Q NOT www eaton com 423...
Страница 493: ...EMR 4000 IM02602009E Motor Protection Curves Motor Protection Curve Example 1 www eaton com 493...
Страница 494: ...EMR 4000 IM02602009E Motor Protection Curve Example 2 without RTDs www eaton com 494...
Страница 495: ...EMR 4000 IM02602009E Motor Protection Curve Example 3 with RTDs www eaton com 495...