EMR-4000
IM02602009E
Ex CLOSE/OPEN
If the switchgear should be opened or closed by an external signal, the User can assign one signal that will trigger the
CLOSE and one signal that will trigger the OPEN command (e.g. digital inputs or output signals of the Logics). An
OPEN command has priority. CLOSE commands are slope oriented, OPEN commands are level oriented.
Synchronized Switching*
*=availability depends on ordered device type
Before a switchgear may connect two mains sections, synchronizm of these sections must be assured.
In the menu [Synchronous Switching] the parameter »Synchronizm« defines which signal indicates synchronizm.
If the synchronizm condition shall be evaluated by the internal Synch-Check module the signal
»Sync. Ready to Close«
(release by synch-check module) has to be assigned. Alternatively a digital input or a logic output can be assigned.
In the synchronization mode “Generator-to-System” additionally the synchronizm request has to be assigned in the
menu [Protection Para\Global Prot Para\Sync].
If a synchronizm signal is assigned, the switching command will only be executed, when the synchronizm signal will
become true within the maximum supervision time »
t-MaxSyncSuperv«. This supervision time will be started with the
issued CLOSE command. If no synchronizm signal has been assigned, the synchronizm release is permanently.
www.eaton.com
407
Содержание EMR-4000
Страница 61: ...EMR 4000 IM02602009E Ethernet RJ45 Terminal Marking www eaton com 61 1 8 TxD TxD RxD N C N C RxD N C N C...
Страница 423: ...EMR 4000 IM02602009E Name Description Logic LE23 Out inverted Signal Negated Latched Output Q NOT www eaton com 423...
Страница 493: ...EMR 4000 IM02602009E Motor Protection Curves Motor Protection Curve Example 1 www eaton com 493...
Страница 494: ...EMR 4000 IM02602009E Motor Protection Curve Example 2 without RTDs www eaton com 494...
Страница 495: ...EMR 4000 IM02602009E Motor Protection Curve Example 3 with RTDs www eaton com 495...