EMR-4000
IM02602009E
Global Protection Parameters of the URTD Module
Parameter
Description
Setting range
Default
Menu path
Force Mode
By means of this function the normal Relay Output States
can be overwritten (forced) in case that the Relay Output
is not in a disarmed state. The relays can be set from
normal operation (relay works according to the assigned
signals) to "force energized" or "force de-energized"
state.
Permanent,
Timeout
Permanent
[Service
/Test Mode (Prot
inhibit)
/WARNING! Cont?
/URTD]
t-Timeout Force
The Output State will be set by force for the duration of
this time. That means, for the duration of this time, the
Relay Output does not show the state of the signals that
are assigned on it.
Only available if: Mode = Timeout DISARM
0.00 - 300.00s
0.03s
[Service
/Test Mode (Prot
inhibit)
/WARNING! Cont?
/URTD]
Temperature Unit
Temperature Unit
Celsius,
Fahrenheit
Celsius
[System Para]
URTD Signals (Output States)
Signal
Description
WD1 Superv
Signal: Supervision Channel WD1
WD2 Superv
Signal: Supervision Channel WD2
WD3 Superv
Signal: Supervision Channel WD3
WD4 Superv
Signal: Supervision Channel WD4
WD5 Superv
Signal: Supervision Channel WD5
WD6 Superv
Signal: Supervision Channel WD6
MB1 Superv
Signal: Supervision Channel MB1
MB2 Superv
Signal: Supervision Channel MB2
LB1 Superv
Signal: Supervision Channel LB1
LB2 Superv
Signal: Supervision Channel LB2
Aux1 Superv
Signal: Supervision Channel Aux1
Aux2 Superv
Signal: Supervision Channel Aux2
Superv
Signal: URTD Supervision Channel
active
Signal: URTD active
Outs forced
Signal: The State of at least one Relay Output has been set by force. That means that the state of
at least one Relay is forced and hence does not show the state of the assigned signals.
www.eaton.com
735
Содержание EMR-4000
Страница 61: ...EMR 4000 IM02602009E Ethernet RJ45 Terminal Marking www eaton com 61 1 8 TxD TxD RxD N C N C RxD N C N C...
Страница 423: ...EMR 4000 IM02602009E Name Description Logic LE23 Out inverted Signal Negated Latched Output Q NOT www eaton com 423...
Страница 493: ...EMR 4000 IM02602009E Motor Protection Curves Motor Protection Curve Example 1 www eaton com 493...
Страница 494: ...EMR 4000 IM02602009E Motor Protection Curve Example 2 without RTDs www eaton com 494...
Страница 495: ...EMR 4000 IM02602009E Motor Protection Curve Example 3 with RTDs www eaton com 495...