EMR-4000
IM02602009E
Parameter
Description
Setting range
Default
Menu path
MaintMode
Manually
Arc Flash Reduction Maintenance Switch Mode: Manual
Activation of the Arc Flash Reduction Mode
Only available if: Maint Mode = Activation Manually
Maint Mode inacti-
ve,
Activation via
Comm,
Activation via DI,
Inactive,
Active
Inactive
[Service
/MaintMode
Manually]
Program Mode
Bypass
Short-period bypass of the Program Mode.
Inactive,
Active
Inactive
[System Para]
CAUTION: Manually rebooting the device will release the Supervision
Contact.
Global Protection Parameters of the System
Parameter
Description
Setting range
Default
Menu path
PSet-Switch
Switching Parameter Set
PS1,
PS2,
PS3,
PS4,
PSS via Inp fct,
PSS via Comm
PSS via Inp fct
[Protection Para
/PSet-Switch]
PS1: Activated by
This Setting Group will be the active one if: The
Parameter Setting Group Switch is set to "Switch via
Input" and the other three input functions are inactive at
the same time. In case there is more than one input
function active, no Parameter Setting Group Switch will
be executed. In case all input functions are inactive, the
device will keep working with the Setting Group that was
activated lastly.
Only available if: PSet-Switch = PSS via Inp fct
1..n, PSS
Sys.Maint Mode
Inactive
[Protection Para
/PSet-Switch]
www.eaton.com
235
Содержание EMR-4000
Страница 61: ...EMR 4000 IM02602009E Ethernet RJ45 Terminal Marking www eaton com 61 1 8 TxD TxD RxD N C N C RxD N C N C...
Страница 423: ...EMR 4000 IM02602009E Name Description Logic LE23 Out inverted Signal Negated Latched Output Q NOT www eaton com 423...
Страница 493: ...EMR 4000 IM02602009E Motor Protection Curves Motor Protection Curve Example 1 www eaton com 493...
Страница 494: ...EMR 4000 IM02602009E Motor Protection Curve Example 2 without RTDs www eaton com 494...
Страница 495: ...EMR 4000 IM02602009E Motor Protection Curve Example 3 with RTDs www eaton com 495...