Values of the Frequency Protection Module
Value
Description
Default
Size
Menu path
nPickups
Number of alarms since last reset.
0
0 - 9999999999 [Operation
/History
/PickupCr]
nTripCmds
Number of trip commands since last reset.
0
0 - 9999999999 [Operation
/History
/TripCmdCr]
Commissioning: Overfrequency [ANSI 81O]
Object to be tested:
All configured overfrequency protection stages.
Necessary means:
Three-phase voltage source with variable frequency; and
Timer
Procedure:
Testing the threshold values
Keep on increasing the frequency until the respective frequency element is activated;
Note the frequency value; and
Disconnect the test voltage.
Testing the trip delay
Set the test voltage to nominal frequency and
Now connect a frequency jump (activation value) and then start a timer. Measure the tripping time at the relay
output.
Testing the fallback ratio:
Reduce the measuring quantity to less than 99.95% of the trip value (or 0.05% fn). The relay must only fall back at
99.95% of the trip value at the earliest (or 0.05% fn).
Successful test result:
Permissible deviations/tolerances can be taken from the Technical Data.
www.eaton.com
640
Содержание EMR-4000
Страница 61: ...EMR 4000 IM02602009E Ethernet RJ45 Terminal Marking www eaton com 61 1 8 TxD TxD RxD N C N C RxD N C N C...
Страница 423: ...EMR 4000 IM02602009E Name Description Logic LE23 Out inverted Signal Negated Latched Output Q NOT www eaton com 423...
Страница 493: ...EMR 4000 IM02602009E Motor Protection Curves Motor Protection Curve Example 1 www eaton com 493...
Страница 494: ...EMR 4000 IM02602009E Motor Protection Curve Example 2 without RTDs www eaton com 494...
Страница 495: ...EMR 4000 IM02602009E Motor Protection Curve Example 3 with RTDs www eaton com 495...