EMR-4000
IM02602009E
Profibus
Profibus
Part 1: Configuration of the Devices
Call up
»Device parameter/Profibus« and set the following communication parameter:
Slave-address, to allow clear identification of the device.
In addition to that the Master has to be provided with the GSD-file. The GSD-file can be taken from the Product-CD.
Part 2: Hardware Connection
For hardware connection to the control system, there is optional an D-SUB interface at the rear side of the
device.
Connect bus and device (wiring).
Up to 123 slaves can be connected.
Terminate the Bus by means of an Terminate Resistor.
Error Handling
Information on physical communication errors, such as:
Baudrate Error
can be obtained from the event recorder or the status display.
Error Handling – Status LED at the rear side
The Profibus D-SUB interface at the rear side of the device is equipped with an status LED.
Baud Search -> red flashing
Baud Found -> green flashing
Data Exchange -> green
No Profibus/Unplugged, not connected -> red
www.eaton.com
264