EMR-4000
IM02602009E
Device Planning Parameters of the Programmable Logic
Parameter
Description
Options
Default
Menu path
No of Equations:
Number of required Logic Equations:
0,
5,
10,
20,
40,
80
20
[Device Planning]
Global Protection Parameter of the Programmable Logic
Parameter
Description
Setting range
Default
Menu path
LE1.Gate
Logic gate
AND,
OR,
NAND,
NOR
OR
[Logic
/LE 1]
LE1.IN1
Assignment of the Input Signal
1..n, Assignment
List
Logic.LE2.Gate
Out
[Logic
/LE 1]
LE1.Inverting1
Inverting the input signals.
Only available if an input signal has been assigned.
Inactive,
Active
Inactive
[Logic
/LE 1]
LE1.IN2
Assignment of the Input Signal
1..n, Assignment
List
Logic.LE3.Gate
Out
[Logic
/LE 1]
LE1.Inverting2
Inverting the input signals.
Only available if an input signal has been assigned.
Inactive,
Active
Inactive
[Logic
/LE 1]
LE1.IN3
Assignment of the Input Signal
1..n, Assignment
List
Logic.LE4.Gate
Out
[Logic
/LE 1]
www.eaton.com
795
Содержание EMR-4000
Страница 61: ...EMR 4000 IM02602009E Ethernet RJ45 Terminal Marking www eaton com 61 1 8 TxD TxD RxD N C N C RxD N C N C...
Страница 423: ...EMR 4000 IM02602009E Name Description Logic LE23 Out inverted Signal Negated Latched Output Q NOT www eaton com 423...
Страница 493: ...EMR 4000 IM02602009E Motor Protection Curves Motor Protection Curve Example 1 www eaton com 493...
Страница 494: ...EMR 4000 IM02602009E Motor Protection Curve Example 2 without RTDs www eaton com 494...
Страница 495: ...EMR 4000 IM02602009E Motor Protection Curve Example 3 with RTDs www eaton com 495...