EMR-4000
IM02602009E
Configuration of the Average Value Calculation
Configuration of the Current Based Average Value Calculation*
*=Availability depends on the ordered device code.
Current based Average Values and Peak Values
Time period for the
calculation of the
average and peak values
Start options
Reset of the average and
peak values
Configuration Options
Where to configure?
In [Device Para\
Statistics\
Demand\
Current Demand]
sliding:
(sliding: average calculation
based on sliding period)
fixed:
(fixed: Average calculation is
reset by the end of the period,
that means with the next starting
period)
duration:
(fixed or sliding period)
Start Fct:
(The average values are
calculated based on the time
period between two rising edges
ot this signal)
Res Fc
(e.g. via Digital Input in order to
reset the average values in
advance (before the next rising
edge of the start signal). This
applies to option »Start FC« only.
Trip (command) option to limit
the average current demand:
Yes
Please refert to chapter »System Alarms«
View average values and peak
values
Where? Within menu [Operation\Statistics\Demand]
www.eaton.com
155
Содержание EMR-4000
Страница 61: ...EMR 4000 IM02602009E Ethernet RJ45 Terminal Marking www eaton com 61 1 8 TxD TxD RxD N C N C RxD N C N C...
Страница 423: ...EMR 4000 IM02602009E Name Description Logic LE23 Out inverted Signal Negated Latched Output Q NOT www eaton com 423...
Страница 493: ...EMR 4000 IM02602009E Motor Protection Curves Motor Protection Curve Example 1 www eaton com 493...
Страница 494: ...EMR 4000 IM02602009E Motor Protection Curve Example 2 without RTDs www eaton com 494...
Страница 495: ...EMR 4000 IM02602009E Motor Protection Curve Example 3 with RTDs www eaton com 495...