EMR-4000
IM02602009E
Parameter
Description
Setting range
Default
Menu path
Reset-PF
This setting is the power factor, at which the relay will
reset the power factor trip. It is like setting a hysteresis
for the Trigger setting.
0.5 - 0.99
0.9
[Protection Para
/<1..4>
/Power Factor-Prot
/PF-55D[1]]
t-trip
Tripping delay
0.00 - 300.00s
0.00s
[Protection Para
/<1..4>
/Power Factor-Prot
/PF-55D[1]]
t-Pickup Comp
Pre-trigger time for the Compensation Signal. When this
timer is elapsed the compensation signal will be
activated.
0.00 - 300.00s
5.00s
[Protection Para
/<1..4>
/Power Factor-Prot
/PF-55D[1]]
t-Reset Comp
Reset (Post-trigger) time of the Compensation Signal.
When this timer is elapsed the compensation signal will
be deactivated.
0.00 - 300.00s
5.00s
[Protection Para
/<1..4>
/Power Factor-Prot
/PF-55D[1]]
States of the Inputs of the Power Factor Module
Name
Description
Assignment via
ExBlo1-I
Module Input State: External Blocking
[Protection Para
/Global Prot Para
/Power Factor-Prot
/PF-55D[1]]
ExBlo2-I
Module Input State: External Blocking
[Protection Para
/Global Prot Para
/Power Factor-Prot
/PF-55D[1]]
ExBlo TripCmd-I
Module Input State: External Blocking of the Trip Command
[Protection Para
/Global Prot Para
/Power Factor-Prot
/PF-55D[1]]
www.eaton.com
678
Содержание EMR-4000
Страница 61: ...EMR 4000 IM02602009E Ethernet RJ45 Terminal Marking www eaton com 61 1 8 TxD TxD RxD N C N C RxD N C N C...
Страница 423: ...EMR 4000 IM02602009E Name Description Logic LE23 Out inverted Signal Negated Latched Output Q NOT www eaton com 423...
Страница 493: ...EMR 4000 IM02602009E Motor Protection Curves Motor Protection Curve Example 1 www eaton com 493...
Страница 494: ...EMR 4000 IM02602009E Motor Protection Curve Example 2 without RTDs www eaton com 494...
Страница 495: ...EMR 4000 IM02602009E Motor Protection Curve Example 3 with RTDs www eaton com 495...