EMR-4000
IM02602009E
Set Parameters of the Power Factor Module
Parameter
Description
Setting range
Default
Menu path
Function
Permanent activation or deactivation of module/element. Inactive,
Active
Inactive
[Protection Para
/<1..4>
/Power Factor-Prot
/PF-55D[1]]
ExBlo Fc
Activate (allow) or inactivate (disallow) blocking of the
module/element. This parameter is only effective if a
signal is assigned to the corresponding global protection
parameter. If the signal becomes true, those
modules/elements are blocked that are parameterized
"ExBlo Fc=active".
Inactive,
Active
Inactive
[Protection Para
/<1..4>
/Power Factor-Prot
/PF-55D[1]]
Blo TripCmd
Permanent blocking of the Trip Command of the
module/element.
Inactive,
Active
PF-55D[1]:
Inactive
PF-55D[2]: Active
PF-55A[1]:
Inactive
PF-55A[2]: Active
[Protection Para
/<1..4>
/Power Factor-Prot
/PF-55D[1]]
ExBlo TripCmd Fc
Activate (allow) or inactivate (disallow) blocking of the
module/element. This parameter is only effective if a
signal is assigned to the corresponding global protection
parameter. If the signal becomes true, those
modules/elements are blocked that are parameterized
"ExBlo TripCmd Fc=active".
Inactive,
Active
Inactive
[Protection Para
/<1..4>
/Power Factor-Prot
/PF-55D[1]]
Trig Mode
Trigger Mode. Should the Module be triggered if the
Current Phasor is leading to the Voltage Phasor = Lead?
Or should the Module be triggered if the Current Phasor
is lagging to the Voltage Phasor = Lag?
I leads V,
I lags V
I lags V
[Protection Para
/<1..4>
/Power Factor-Prot
/PF-55D[1]]
Trigger-PF
This is the power factor where the relay will pick up
0.5 - 0.99
0.7
[Protection Para
/<1..4>
/Power Factor-Prot
/PF-55D[1]]
Res Mode
Trigger Mode. Should the Module be triggered if the
Current Phasor is leading to the Voltage Phasor = Lead?
Or should the Module be triggered if the Current Phasor
is lagging to the Voltage Phasor = Lag?
I leads V,
I lags V
I lags V
[Protection Para
/<1..4>
/Power Factor-Prot
/PF-55D[1]]
www.eaton.com
677
Содержание EMR-4000
Страница 61: ...EMR 4000 IM02602009E Ethernet RJ45 Terminal Marking www eaton com 61 1 8 TxD TxD RxD N C N C RxD N C N C...
Страница 423: ...EMR 4000 IM02602009E Name Description Logic LE23 Out inverted Signal Negated Latched Output Q NOT www eaton com 423...
Страница 493: ...EMR 4000 IM02602009E Motor Protection Curves Motor Protection Curve Example 1 www eaton com 493...
Страница 494: ...EMR 4000 IM02602009E Motor Protection Curve Example 2 without RTDs www eaton com 494...
Страница 495: ...EMR 4000 IM02602009E Motor Protection Curve Example 3 with RTDs www eaton com 495...