INSTALLATION INSTRUCTIONS FOR SYMCOM’S 

MOTORSAVER

®

MODEL 460

BE SURE POWER IS DISCONNECTED PRIOR TO INSTALLATION!!

FOLLOW NATIONAL, STATE AND LOCAL CODES!

CONNECTIONS

1. Mount the MOTORSAVER

®

in a convenient location in or near the motor control panel.  If the 

location is wet or dusty, then the MOTORSAVER

®

should be mounted in a NEMA 4 or 12 

enclosure. The 460 can be mounted to a back panel using two #6 or #8 x 5/8 screws or can be 
snapped on to a DIN rail.

2. Connect L1, L2 and L3 on the MotorSaver’s terminal strip to the 

LINE SIDE

of the motor starter.  

(See Figure No. 1).

3. Connect the output relay to the circuitry to be controlled. Connect the normally open contact in 

series with the magnetic coil of the motor starter as shown in Figure No. 1 for motor control. 
Connect normally closed contact in control circuit as shown in figure No. 2 for alarm operation.

Figure No. 1: Motor Control Wiring Diagram

LIGHT

Figure No. 2: Alarm Wiring Diagram

2880 North Plaza Drive, Rapid City, SD 57702 • (800) 843-8848

Summary of Contents for MOTORSAVER 460

Page 1: ...wo 6 or 8 x 5 8 screws or can be snapped on to a DIN rail 2 Connect L1 L2 and L3 on the MotorSaver s terminal strip to the LINE SIDE of the motor starter See Figure No 1 3 Connect the output relay to the circuitry to be controlled Connect the normally open contact in series with the magnetic coil of the motor starter as shown in Figure No 1 for motor control Connect normally closed contact in cont...

Page 2: ...ng a motor above a 1 voltage unbalance as determined by the following formula without derating the motor Voltage Unbalance Maximum Deviation from the Average Average x 100 The NEMA MG1 standard also recommends against operating a motor above a 5 voltage unbalance under any circumstances Therefore a 5 setting on UB is a good place to start but SymCom recommends consulting the motor manufacturer for...

Page 3: ...e t a l u c l a c d n a s e g a t l o v e n i l g n i m o c n i e r u s a e M e c n a l a b n u e g a t l o v s e t a c i d n I e h t n o t e s e c n a l a b n u e h t d e e c x e t o n s e o d e c n a l a b n u e g a t l o v f I 1 e g a p n o n w o h s s a t a m o C m y S l l a c 0 6 4 e h t t e s e r t o n s e o d s i h t f I n o t t u b t e s e r l a u n a m e h t g n i s s e r p y r t t n o r ...

Page 4: ... UB 1 second fixed Restart Delay Time After a Fault 1 500 seconds adjustable After a Complete Power Loss 1 500 seconds adjustable Output Contact Rating 1 Form C 10 A General Purpose 240 VAC Pilot Duty 480VA 240 VAC B300 Power Consumption 6 Watts Max Weight 14 oz Enclosure polycarbonate Terminal Torque 6lbs in Wire Type Stranded or solid 12 20 AWG one per terminal Safety Marks UL UL508 CE IEC 60947...