Safety Relay s from IDEM           SCR-3 

Safety Relay s from IDEM           SCR-2H 

H02 

Ver. A 

E61-328-00 

• 

Up to PL e, SILCL 3, category 4 

Correct Use 

The  SCR-2H  2-hand  safety  relay  is  an  extremely  com-
pact,  universal  safety  two-hand  control  unit.  It  com-
plies  with  EN574,  Typ  III  C,  and  is  intended  for  use  in 
safety circuits that are designed in accordance with EN 
60204-1,  e.g.  on  presses,  punches  and  bending  tools. 
Due to  the internal  error monitoring, the 2-hand  safety 
relay  can  be  used,  despite  very  compact  dimensions, 
for all  applications up  to  the  highest safety  category 4 
and PL e according to EN ISO 13849-1, SILCL 3 accord-
ing to EN 62061 or Typ III C according to EN 574.

 

Features 

• 

2 safe, redundant relay outputs 

• 

Cyclical monitoring of the output contacts 

• 

Feedback loop for monitoring downstream contactors or 
expansion modules 

• 

Short circuit and earth fault monitoring 

• 

Extrem compact housing 

Function 

The  IDEM  2-hand  safety  relay  SCR-2H

 

is  suitable  for  set-

ting  up  and  monitoring  two-hand  circuits  and  is  used  to 
protect  the  operators.  Dangerous  work  steps  can  only  be 
triggered  when  both  two-hand  buttons  connected  are  ope-
rated simultaneously, i.e. within 0.5 s. 

It is to be  ensured  a single fault  or  a  malfunction does  not 
result  in  the  loss  of  the  safety  function  and  every  fault  is 
detected  by  the  cyclic  self-monitoring  at  the  latest  prior  to 
the next actuation. 

When  the  operating  voltage  is  applied  to  A1-A2  and  the 
feedback  loop  X1-X2  is  closed,  the  SCR-2H  is  ready  for 
use. To be able to initiate a switching operation, the output 
relays must be de-energized. The output relays only switch 
to  the  energized  position  when  the  two-hand  buttons  T1 
and T2 are operated simultaneously, i.e. within 0.5 s.  

Fig. 1 Block diagram SCR-2H 

 

• 

All relevant sefety regulations and standards are to be 
observed. 

• 

The overall concept of the control system in which the 
device is incorporated must be validated by the user. 

• 

Failure to observe the safety regulations can result in 
death, serious injury and serious damage. 

• 

Note down the version of the product (see label “Ver. X”) 
and check it prior to every commissioning of a new de-
vice. If the version has changed, the overall concept of 
the control system in which the device is incorporated 
must be validated again by the user. 

Installation 

As per DIN EN 60204-1, the device is intended for installa-
tion in control cabinets with a minimum degree of protection 
of IP54. It is mounted on a 35 mm DIN rail according to DIN 
EN 60715 TH35. 

Safety Precauti-
ons 

• 

Installation and commissioning of the device must be 
performed 

only by authorized personnel

• 

Observe the country-specific regulations when installing 
the device. 

• 

The electrical connection of the device is only allowed to 
be made with the device isolated. 

• 

The wiring of the device must comply with the instruc-
tions in this user information, otherwise there is a risk 
that the safety function will be lost. 

• 

It is not allowed to open the device, tamper with the 
device or bypass the safety devices. 

Fig. 2 Installation/removal 

Electrical Connec-
tion 

• 

When the 24 V version is used, a safety transformer 
according to EN 61558-2-6 or a power supply unit with 
electrical isolation from the mains must be connected. 

• 

External fusing of the safety contacts (10 A gG) must be 
provided. 

• 

A maximum length of the control lines of 1000 meters 
with a line cross section of 0.75 mm

2

 must not be excee-

ded. 

• 

The line cross section must not exceed 2.5 mm

2

• 

If the device does not function after commissioning, it 
must be returned to the manufacturer unopened. Ope-
ning the device will void the warranty. 

13 23

14 24

K2

K1

SCR-2H

Fig. 3 Connections 

A1: 

 Power supply 

A2. 

 Power supply 

S11:  

Control line T1 

S12: 

Control line T1 

S13: 

Control line T1 

S21: 

Control line T2 

S22: 

Control line T2 

S23: 

Control line T2 

X1; X2: 

Feedback loop 

13-14:  

Safety contact 1 

23-24:  

Safety contact 2 

The output relays are not switched if: 

• 

only one two-hand button is actuated or the time between the actuation of the 2 two-hand buttons is greater than 0.5 s, 

• 

the feedback loop is open (fault in the external contactor), 

• 

another error (short circuit, cable break, error in the switching device) has occurred. 

When T1 and/or T2 are/is released, the output relays opens immediately. In order to trigger a new operation, both two-hand 

buttons must first be released and the feedback loop must be closed. 

(not for plug-in terminals) 

 

SCR-2H 