DEMA DigiLine 400 Series Protection Relays   

         

Page 1 of 11 

                                                                  

           Quick Start Guide V1.0 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Содержание DEMA DigiLine 400 Series

Страница 1: ...DEMA Role San ve Tic A S DEMA DigiLine 400 Series Protection Relays Page 1 of 11 Quick Start Guide V1 0 ...

Страница 2: ... A S DEMA DigiLine 400 Series Protection Relays Page 2 of 11 Quick Start Guide V1 0 Versions Rev No Comp Relay SW Version Cause of Revision Committer Date V1 0 1 1 9 2 and later First Publication Cihangir ODABAŞ 03 04 2019 ...

Страница 3: ...DigiLine 400 Series Protection Relays Page 3 of 11 Quick Start Guide V1 0 1 Contents 2 Power Up the Relay 4 3 Start Communicating with the Relay 5 4 Configure the Relay with DigiConnect 400 7 5 Configure the Relay with WebServer 10 ...

Страница 4: ...y Power Supply Specifications Description Value Nominal auxiliary voltage 48 240 Vac 24 240 Vdc Operating range of auxiliary voltage 36 264 Vac 22 264 Vdc Nominal frequency for AC voltage 50 60 Hz To power up the relay proper voltage needs to be supplied to the rear connectors To identify which ports should be used please follow connector plan on the side of the relay Figure 1 Power pins are on th...

Страница 5: ... 168 2 215 Rear 2 ports Copper Standard Ethernet CAT 5 with RJ 45 2 port Fiber Optics 100 Mbits s IP is configurable 4 port shares same IP Ports are bridged Front port Ethernet has fixed IP 192 168 2 215 to supply easy and fast communication through all DigiLine 400 series To change Rear Port IP address please follow the instructions below Enter the menu of ethernet settings on the device GUI Foll...

Страница 6: ...ter options of ethernet ports Figure 3 Right click Ethernet and select Properties Figure 4 Open Internet Protocol Version 4 TCP IPv4 properties Give an IP address to your PC with careful of below warnings Warning 1 Do not give the same IP to your PC with relays Warning 2 PC s IP should be on same subnet with relays Same subnet means first three region of IP addresses should be matched For example ...

Страница 7: ...e generated for future use as well Executing the program is easy as well Please run DigiConnect400 exe It will run without any installation First appearance is shown in Figure 5 Please select your Language Dil to English İngilizce Figure 5 DigiConnect 400 Language Settings Create your first project with Project New After giving a proper name Project Tree will appear To add new items to your tree R...

Страница 8: ... connect it with selected selection directly When offline mode is selected selection is recorded and used when user requested Setting could be changed after adding on tree Right click the Device and select Change IP Configuration Type is used only in Offline mode Configuration type defines what kind of settings template for new added device Standard Configuration is empty template If Example confi...

Страница 9: ... A S DEMA DigiLine 400 Series Protection Relays Page 9 of 11 Quick Start Guide V1 0 Figure 9 Parameter Setting Screen Edited and not saved settings are emphasized with color Make sure to save settings and sent it to device ...

Страница 10: ... relay via Web Server Open web browser of any kind and enter the relay IP address Figure 10 is entering screen of the Web Server Enter user name and password User email dema Password dema Figure 10 Web Server Enter Screen Webserver is communicating with the relay in real time Measurements could be observed Setting could be seen and changed directly Figure 11 shows tree and menus after entering Web...