background image

Specifications

Operating Voltage Range: 

8.5 to 35 VDC

Maximum Operating Current: 

25mA

Relay Contacts: 

2A at 35 VDC

Operating Temperature Range: 

32° to 131° F (0° to 55° C) 

Operating Humidity Range: 

5% to 85% non-condensing

Dimensions: 2

1

2

˝ x 2

1

2

˝ x 1˝

Wire connections: 

18 AWG stranded, tinned, 16˝ long

RRS-MOD Reversing Relay/Synchronization Module

3825 Ohio Avenue, St. Charles, Illinois 60174

1-800-SENSOR2, FAX: 630-377-6495

www.systemsensor.com

General Description

The RRS-MOD polarity reversing relay/synchronization 
module is intended for use with 2-wire and 4-wire i3 se-
ries detectors equipped with a built-in sounder, models 
2WTA-B, 4WTA-B, 4WTAR-B, and 4WITAR-B. It is designed 
to allow all the detectors in the same loop to sound when 
one of the detectors goes into alarm, and to synchronize 
their audible output. The RRS-MOD also allows the silenc-
ing of the detector sounders from the alarm control panel.

The RRS-MOD may be used with an alarm zone that pro-
vides coded output for fire and continuous output for 
burglary. By default the RRS-MOD’s switch is set to “off”. 
Therefore, the RRS-MOD will only trigger when the alarm 
output is coded. In this manner, smoke detectors will only 
sound from the result of a fire, and not from a burglary 
alarm. In this mode, the detectors will provide a synchro-
nized, coded output.

The RRS-MOD can also be set to only trigger on continu-
ous alarm zone signals by selecting the switch to “on”. 
In this mode, the detectors will provide a synchronized, 
coded output.

NOTICE:

 This manual shall be left with the owner/user of

this equipment.

Installation

Choose a mounting location in the control panel within 
reach of the provided wire leads. Use a water/isopropyl 
alcohol mixture (50/50) to clean the mounting surface. 
Allow surface to dry and remove paper backing from the 
Velcro and catch. Stick the Velcro in the panel and the catch 
on the back of the module, then mount the module inside 
the control panel. Route terminals to the appropriate termi-
nals as noted below.

WARNING

When calculating total current draw of the control panel, 
remember to add current consumption (25mA) for the po-
larity  reversal relay module (RRS-MOD). IMPORTANT: If 
the fire alarm output signal is coded, set the switch on the 
RRS-MOD to “OFF”. If the fire alarm output signal is con-
tinuous, set the switch to “ON”.

Wiring

IMPORTANT: All polarities must be observed!

1.  Connect the RRS-MOD module trigger wire to the fire 

alarm output terminals.

    A. Alarm/Bell output: (Figures 1 and 2)
      Connect the purple wire to the Alarm or Bell output.
    B. Alarm relay, normally open contact: (Figures 3 and 4)
   1. 

 

Connect one end of the alarm relay contact out-
put to positive auxiliary or detector power fire 
alarm output.

   2. 

 

Connect the purple wire to the other end of the 
alarm relay contact output.

2.  Connect the red and black wires to the panel auxiliary or 

detector power (red to positive, black to negative).

3.   

2-wire models

   Connect the yellow and orange wires to the panel initiat-

ing circuit (yellow to positive, orange to negative).

 

4-wire models

   Connect the yellow and orange wires to the panel detec-

tor power circuit (yellow to positive, orange to negative).

4. 

2-wire models

   Connect the brown and white wires to the smoke de-

tector power supply input (brown to positive, white 
to negative).

 

4-wire models

   Connect the brown and white wires to the smoke detec-

tor power circuit (brown to positive, white to negative).

NOTE: 

In an alarm condition, a wiring-fault

trouble state may also register at the panel

when the RRS-MOD is used.

INSTALLATION AND MAINTENANCE INSTRUCTIONS

Series

D500-44-00 1 

I56-2203-003

I56-2203-003

Summary of Contents for i3 Series

Page 1: ...ohol mixture 50 50 to clean the mounting surface Allow surface to dry and remove paper backing from the Velcro and catch Stick the Velcro in the panel and the catch on the back of the module then mount the module inside the control panel Route terminals to the appropriate termi nals as noted below WARNING When calculating total current draw of the control panel remember to add current consumption ...

Page 2: ...UX POWER OR DETECTOR POWER INITIATING DEVICE CIRCUIT BELL ALARM CIRCUIT positive signal in alarm state PURPLE T YELLOW IN ORANGE IN RED PWR BLACK PWR BROWN OUT WHITE OUT 1 IN 2 OUT 3 IN OUT 4 N O 5 C 1 IN 2 OUT 3 IN OUT 4 N O 5 C ALARM RELAY NO Contact UL LISTED ALARM CONTROL PANEL 2 WIRE INITIATING DEVICE CIRCUIT PURPLE T AUX POWER YELLOW IN ORANGE IN RED PWR BLACK PWR BROWN OUT WHITE OUT EOL OPT...

Page 3: ...T 4 RA 5 C 470Ω 1 2 WATT RESISTOR NEEDED FOR PANEL TO RESET D500 44 00 3 I56 2203 003 S0104 00 Figure 4 4 Wire system triggered from alarm relay contact UL LISTED ALARM CONTROL PANEL DETECTOR POWER AUX POWER OR DETECTOR POWER INITIATING DEVICE CIRCUIT ALARM RELAY NO Contact PURPLE T YELLOW IN ORANGE IN RED PWR BLACK PWR BROWN OUT WHITE OUT EOL EOL RELAY SHOWN ENERGIZED 1 IN 2 OUT 3 IN OUT 4 N O 5 ...

Page 4: ...efore testing notify the proper authorities that the system is undergoing maintenance and will temporarily be out of service Test in accordance with NFPA 72 test methods inspections and testing frequency 1 Confirm that all smoke detectors connected to the RRS MOD module s contain a sounder and the sounders are activated upon power reversal 2 Initiate an alarm with one of the smoke detectors con nec...

Reviews: