15-4
Cisco ONS 15454 Procedure Guide, R5.0
December 2004
Chapter 15 Maintain the Node
NTP-A108 Back Up the Database
Step 11
If you washed the filter, allow it to completely air dry for at least eight hours.
Warning
Do not put a damp filter back in the ONS 15454.
Step 12
Replace the clean filter:
a.
If the air filter is installed in the external filter brackets, slide the dry air filter all the way to the back
of the brackets to complete the procedure.
b.
If the filter is installed below the fan-tray assembly, remove the fan-tray assembly and slide the
dry/clean air filter into the recessed compartment at the bottom of the shelf assembly. Put the front
edge of the air filter flush against the front edge of the recessed compartment. Push the fan tray back
into the shelf assembly.
Caution
If the fan tray does not slide all the way to the back of the shelf assembly, pull the fan tray out and
readjust the position of the reusable filter until the fan tray fits correctly.
Note
On a powered-up ONS 15454, the fans start immediately after the fan-tray assembly is correctly
inserted.
Step 13
To verify that the tray is plugged into the backplane, ensure that the LCD on the front of the fan-tray
assembly is activated and displays node information.
Step 14
Rotate the retractable handles back into their compartments.
Step 15
If you replace the door, also reattach the ground strap.
Step 16
Close and lock the door.
Step 17
Return to your originating procedure (NTP).
Stop. You have completed this procedure.
NTP-A108 Back Up the Database
Purpose
This procedure stores a backup version of the TCC2/TCC2P (software)
database on the workstation running Cisco Transport Controller (CTC)
or on a network server.
Tools/Equipment
None
Prerequisite Procedures
None
Required/As Needed
Required. Cisco recommends performing a database backup at
approximately weekly intervals and prior to and after configuration
changes.
Onsite/Remote
Onsite or remote
Security Level
Maintenance or higher
Содержание ONS 15454 Series
Страница 28: ...Tables xxviii Cisco ONS 15454 Procedure Guide R5 0 December 2004 ...
Страница 44: ...Tasks xliv Cisco ONS 15454 Procedure Guide R5 0 December 2004 ...
Страница 53: ...liii Cisco ONS 15454 Procedure Guide R5 0 December 2004 About this Guide Document Conventions ...
Страница 55: ...lv Cisco ONS 15454 Procedure Guide R5 0 December 2004 About this Guide Document Conventions ...
Страница 126: ...4 14 Cisco ONS 15454 Procedure Guide R5 0 December 2004 Chapter 4 Turn Up Node NTP A256 Set Up SNMP ...
Страница 168: ...5 42 Cisco ONS 15454 Procedure Guide R5 0 December 2004 Chapter 5 Turn Up Network NTP A172 Create a Logical Network Map ...
Страница 304: ...10 8 Cisco ONS 15454 Procedure Guide R5 0 December 2004 Chapter 10 Change Node Settings NTP A87 Change SNMP Settings ...
Страница 410: ...16 4 Cisco ONS 15454 Procedure Guide R5 0 December 2004 Chapter 16 Power Down the Node NTP A114 Power Down the Node ...
Страница 510: ...17 100 Cisco ONS 15454 Procedure Guide R5 0 March 2005 Chapter 17 DLPs A1 to A99 DLP A99 Determine Available VLANs ...
Страница 746: ...20 102 Cisco ONS 15454 Procedure Guide R5 0 March 2005 Chapter 20 DLPs A300 to A399 DLP A399 Install a UBIC H EIA ...
Страница 828: ...A 14 Cisco ONS 15454 Procedure Guide R5 0 December 2004 Appendix A CTC Information and Shortcuts Equipment Inventory ...
Страница 850: ...Index IN 22 Cisco ONS 15454 Procedure Guide R5 0 December 2004 description 4 11 remove 18 23 ...