Name
Range
Step
Default
Description
DC 1…4
Input
signal
select
0: 3PH.Fwd.Act.EP
1: 3PH.Rev.Avt.EP
2:
3PH.Fwd.React.EQ.CAP
3: 3PH.Fwd.React.EQ.IND
4:
3PH.Rev.React.EQ.CAP
5: 3PH.Rev.React.EQ.IND
-
0:
3PH.Fwd.Act.EP
Selects whether the energy is active or reactive,
whether the direction of the energy is forward of
reverse, and whether reactive energy is inductive or
capacitive.
DC 1…4
Input
signal
-1 × 10
6
…1 × 10
6
0.01
-
The total amount of energy consumed.
DC 1…4
Pulse
magnitude
0…1800kW/var
0.005kW/
var
1kW/Var
The set pulse size. An energy pulse is given every
time the set magnitude is exceeded.
DC 1…4
Pulse
length
0…1800s
0.005s
1s
The total length of a control pulse.
DC1…4
Pulses
sent
0…4 294 967 295
1
-
Indicates the total number of pulses sent.
Table. 5.2.3 - 38. DC 1…4 Pulse out settings
Name
Range
Step
Default
Description
DC 1…4 Pulse out
OUT1…OUTx
-
None selected
The selection of the controlled physical outputs.
Power measurements
The following power calculations are available when the voltage and the current cards are available.
Table. 5.2.3 - 39. Three-phase power calculations.
Name
Unit
Range
Step
Description
3PH Apparent power (S)
kVA
-1x10
6
…1x10
6
0.01
The total three-phase apparent power in kilo-volt-ampere
3PH Active power (P)
kW
-1x10
6
…1x10
6
0.01
The total three-phase active power in kilowatts
3PH Reactive power (Q)
kVar
-1x10
6
…1x10
6
0.01
The total three-phase reactive power in kilovars
3PH Apparent power (S MVA)
MVA
-1x10
5
…1x10
5
0.01
The total three-phase apparent power in megawatts
3PH Active power (P MW)
MW
-1x10
5
…1x10
5
0.01
The total three-phase active power in mewatts
3PH Reactive power (QMVar)
MVar -1x10
5
…1x10
5
0.01
The total three-phase active power in megavars
3PH Tan(phi)
-
-1x10
6
…1x10
6
0.01
The direction of three-phase active power
3PH Cos(phi)
-
-1x10
6
…1x10
6
0.01
The direction of three-phase reactive power
3PH Power factor
-
-1x10
6
…1x10
6
0.0001 The three-phase power factor
Table. 5.2.3 - 40. Single-phase power calculations (L1...L3).
Name
Unit
Range
Step
Description
Lx Apparent power (S)
kVA
-1x10
6
…1x10
6
0.01
The apparent power of Phase Lx in kilo-volt-amperes
Lx Active power (P)
kW
-1x10
6
…1x10
6
0.01
The active power of Phase Lx in kilowatts
A
AQ
Q-F205
-F205
Instruction manual
Version: 2.04
© Arcteq Relays Ltd
IM00013
83
Содержание AQ F205
Страница 1: ...AQ F205 Feeder protection IED Instruction manual ...
Страница 2: ......
Страница 379: ...Figure 7 4 245 Example block scheme A AQ Q F205 F205 Instruction manual Version 2 04 Arcteq Relays Ltd IM00013 377 ...
Страница 389: ...Figure 8 7 254 Device installation A AQ Q F205 F205 Instruction manual Version 2 04 Arcteq Relays Ltd IM00013 387 ...