Settable alarms
24 alarms available (two per each alarm channel)
Pick-up
Alarm setting range
Inaccuracy
Reset ratio
101.00…2000.00 deg, setting step 0.1 deg (either < or > setting)
±3 % of the set pick-up value
97 % of the pick-up setting
Operation
Operating time
Typically <500 ms
9.2.1.18 Voltage memory
Table. 9.2.1.18 - 299. Technical data for the voltage memory function.
Measurement inputs
Voltage inputs
U
L1
, U
L2
, U
L3
U
L12
, U
L23
, U
L31
+ U
0
Current inputs (back-up frequency)
Phase current inputs: I
L1
(A), I
L2
(B), I
L3
(C)
Pick-up
Pick-up voltage setting
Pick-up current setting (optional)
2.00…50.00 %U
N
, setting step 0.01 x %U
N
0.01…50.00 × I
N
, setting step 0.01 × I
N
Inaccuracy:
- Voltage
- Current
±1.5 %U
SET
or ±30 mV
±0.5 %I
SET
or ±15 mA (0.10…4.0 × I
SET
)
Operation time
Angle memory activation delay
<20 ms (typically 5 ms)
Maximum active time
0.020…50.000 s, setting step 0.005 s
Inaccuracy:
- Definite time (U
M
/U
SET
ratio >1.05)
±1.0 % or ±35 ms
Angle memory
Angle drift while voltage is absent
±1.0° per 1 second
Reset
Reset ratio:
- Voltage memory (voltage)
- Voltage memory (current)
103 % of the pick-up voltage setting
97 % of the pick-up current setting
Reset time
<50 ms
Note!
• Voltage memory is activated only when all line voltages fall below set pick-up value.
• Voltage memory activation captures healthy situation voltage angles, one cycle before actual
activation (50Hz/20ms before “bolted” fault)
9.2.2 Control functions
9.2.2.1 Setting group selection
Table. 9.2.2.1 - 300. Technical data for the setting group selection function.
Settings and control modes
Setting groups
8 independent, control-prioritized setting groups
A
AQ
Q-F205
-F205
Instruction manual
Version: 2.04
© Arcteq Relays Ltd
IM00013
409
Содержание AQ F205
Страница 1: ...AQ F205 Feeder protection IED Instruction manual ...
Страница 2: ......
Страница 379: ...Figure 7 4 245 Example block scheme A AQ Q F205 F205 Instruction manual Version 2 04 Arcteq Relays Ltd IM00013 377 ...
Страница 389: ...Figure 8 7 254 Device installation A AQ Q F205 F205 Instruction manual Version 2 04 Arcteq Relays Ltd IM00013 387 ...