Event number Event channel
Event block name Event code
Description
4094
63
AR1
62
AR Running (DT) ON
4095
63
AR1
63
AR Running (DT) OFF
The function registers its operation into the last twelve (12) time-stamped registers. The register of the
function records the ON event process data from statuses, commands, etc.
The table below presents the structure of the auto-recloser function's register content.
Table. 5.4.4 - 187. Register content.
Date and
time
Event
code
Setting
group
in use
Inhibit
condition
active
Inhibit
condition
release
Locked
condition
active
Locked
condition
release
AR status
Active
timer
Active
time
dd.mm.yyyy
hh:mm:ss.mss
4032...4095
Descr.
1...8
Inhibit
reason
ON
Inhibit
reason
OFF
Locked
reason
ON
Locked
reason
OFF
The status code
of the auto-
recloser function
Timer
ON
The
value
of the
timer
The auto-recloser function's registers are treated differently than the registers of other functions.
Below is an exhaustive example of how the registers work based on a partial auto-recloser sequence.
First is how the register list is displayed:
Date and time
Registers
dd.mm.yyyy
hh:mm:ss.mss
AR Status: AR is ready, AR is not running, AR2 Requested, Executing Shot 1
AR Timers: No timers running 0.000 s
dd.mm.yyyy
hh:mm:ss.mss
AR Status: AR is ready, AR is not running, Start time counting, AR2 Requested, Executing Shot 1
AR Timers: Start Delay 0.000 s
dd.mm.yyyy
hh:mm:ss.mss
AR Status: AR is ready, AR is running, Start time counting, AR2 Requested, Executing Shot 1
AR Timers: Start Delay 0.000 s
dd.mm.yyyy
hh:mm:ss.mss
AR Status: AR is ready, AR is running, Dead time counting, AR2 Requested, Executing Shot 1
AR Timers: Dead Time 0.195 s
dd.mm.yyyy
hh:mm:ss.mss
AR Status: AR is ready, AR is running, Dead time counting, Reclaim time counting, AR2 Requested,
Executing Shot1
AR Timers: Dead Time -0.270 s
The corresponding event list is as presented below (inc. object and protection events):
dd.mm.yyyy hh:mm:ss.mss
1664
NEF1 Start ON
dd.mm.yyyy hh:mm:ss.mss
1666
NEF1 Trip ON
dd.mm.yyyy hh:mm:ss.mss
4065
AR1 Shot 1 Execute ON
dd.mm.yyyy hh:mm:ss.mss
4037
AR1 AR Reclosing request ON
dd.mm.yyyy hh:mm:ss.mss
4053
AR1 AR2 Request ON
dd.mm.yyyy hh:mm:ss.mss
4081
AR1 Shot start time ON
dd.mm.yyyy hh:mm:ss.mss
4045
AR1 Object "Open" request
dd.mm.yyyy hh:mm:ss.mss
2944
OBJ1 Object Intermediate
dd.mm.yyyy hh:mm:ss.mss
2952
OBJ1 Open request ON
dd.mm.yyyy hh:mm:ss.mss
2955
OBJ1 Open command ON
dd.mm.yyyy hh:mm:ss.mss
4063
AR1 AR Running ON
A
AQ
Q-F205
-F205
Instruction manual
Version: 2.04
© Arcteq Relays Ltd
IM00013
285