Dead time
±1.0 % or ±35 ms (AR delay)
Action time
±1.0 % or ±30 ms (AR delay)
Instant starting time
Instant operation time
Protection activation delay + 15 ms (Prot AR delay)
9.2.2.4 Cold load pick-up (CLPU)
Table. 9.2.2.4 - 303. Technical data for the cold load pick-up function.
Measurement inputs
Current inputs
Phase current inputs: I
L1
(A), I
L2
(B), I
L3
(C)
Current input magnitudes
RMS phase currents
Pick-up
Pick-up current setting
- I
LOW
/I
HIGH
/I
OVER
0.01…40.00 × I
N
, setting step 0.01 × I
N
Reset ratio
97 % of the pick-up current setting
Inaccuracy:
- Current
±0.5 %I
SET
or ±15 mA (0.10…4.0 × I
SET
)
Operation time
Definite time function operating time settings:
- t
SET
- t
MAX
- t
MIN
0.000…1800.000 s, setting step 0.005 s
0.000…1800.000 s, setting step 0.005 s
0.000…1800.000 s, setting step 0.005 s
Inaccuracy:
- Definite time (I
M
/I
SET
ratio = 1.05/0.95)
±1.0 % or ±45 ms
Instant operation time
CLPU activation and release
<45 ms (measured from the trip contact)
No
Notte!
e!
• A single-phase current (IL1, IL2 or IL3) is enough to prolong or release the blocking during an
overcurrent condition.
9.2.2.5 Switch-on-to-fault (SOTF)
Table. 9.2.2.5 - 304. Technical data for the switch-on-to-fault function.
Initialization signals
SOTF activate input
Any IED blocking input signal (Object closed signal, etc.)
Pick-up
SOTF function input
Any IED blocking input signal (I> or similar)
SOTF activation time
Activation time
<40 ms (measured from the trip contact)
SOTF release time
Release time setting
0.000…1800.000 s, setting step 0.005 s
Inaccuracy:
- Definite time
±1.0 % or ±30 ms
SOTF instant release time
<40 ms (measured from the trip contact)
A
AQ
Q-F205
-F205
Instruction manual
Version: 2.04
© Arcteq Relays Ltd
IM00013
411
Содержание AQ F205
Страница 1: ...AQ F205 Feeder protection IED Instruction manual ...
Страница 2: ......
Страница 379: ...Figure 7 4 245 Example block scheme A AQ Q F205 F205 Instruction manual Version 2 04 Arcteq Relays Ltd IM00013 377 ...
Страница 389: ...Figure 8 7 254 Device installation A AQ Q F205 F205 Instruction manual Version 2 04 Arcteq Relays Ltd IM00013 387 ...