dd.mm.yyyy hh:mm:ss.mss
2954
OBJ1 Open request OFF
dd.mm.yyyy hh:mm:ss.mss
1665
NEF1 Start OFF
dd.mm.yyyy hh:mm:ss.mss
1667
NEF1 Trip OFF
dd.mm.yyyy hh:mm:ss.mss
4038
AR1 AR Reclosing request OFF
dd.mm.yyyy hh:mm:ss.mss
2945
OBJ1 Open request
dd.mm.yyyy hh:mm:ss.mss
2956
OBJ1 Open command OFF
dd.mm.yyyy hh:mm:ss.mss
4082
AR1 Shot start time OFF
dd.mm.yyyy hh:mm:ss.mss
4083
AR1 Dead time ON
dd.mm.yyyy hh:mm:ss.mss
2963
OBJ1 Status change OFF
dd.mm.yyyy hh:mm:ss.mss
4044
AR1 Object "Close" request
dd.mm.yyyy hh:mm:ss.mss
2957
OBJ1 Close request ON
dd.mm.yyyy hh:mm:ss.mss
2958
OBJ1 Close Fail
dd.mm.yyyy hh:mm:ss.mss
2959
OBJ1 Close request OFF
dd.mm.yyyy hh:mm:ss.mss
2960
OBJ1 Close command ON
dd.mm.yyyy hh:mm:ss.mss
2962
OBJ1 Status change ON
dd.mm.yyyy hh:mm:ss.mss
2944
OBJ1 Object Intermediate
dd.mm.yyyy hh:mm:ss.mss
2946
OBJ1 Object Close
dd.mm.yyyy hh:mm:ss.mss
2961
OBJ1 Close command OFF
dd.mm.yyyy hh:mm:ss.mss
4087
AR1 Shot reclaim time ON
As these tables show, the register list complement the information from event lists when the control has
encountered some unexpected behavior. The example above shows that the object had issues
executing the "Close" command, which caused the dead time to be 270 ms longer that its set value.
The reason for this behavior can be verified from the object control and monitoring function's registers.
The example below shows that the object was not ready when it received the closing request from the
auto-recloser function and kept the request pending until it was ready to execute the "Close" command.
dd.mm.yyyy
hh:mm:ss.mss
Object Open, WD In, Open Allowed, Close Allowed, Object Ready, Sync Ok, Obj open time: 0.025 s
dd.mm.yyyy
hh:mm:ss.mss
Object Open, WD In, Object not ready for Close request, Open Allowed, Close Allowed, Object Not
Ready, Sync Ok
dd.mm.yyyy
hh:mm:ss.mss
Object Open, WD In, Close request from Auto-recloser, Close pending due to: Close wait for Ready, Open
Allowed, Close Allowed, Object Not Ready, Sync Ok
dd.mm.yyyy
hh:mm:ss.mss
Object Open, WD In,Open Allowed, Close Allowed, Object Ready, Sync Ok
dd.mm.yyyy
hh:mm:ss.mss
Object Closed, WD In, Open Allowed, Close Allowed, Object Ready, Sync Ok , Obj close time: 0.030 s
A
Aut
uto-r
o-recloser opera
ecloser operation count
tion counters
ers
The auto-recloser function keeps statistical track of the operated auto-reclosing cycles as well as of
successful and failed shots.
The function records the following counters:
• Shot 1…5 started
• Shot 1…5 requested by AR1…5
A
AQ
Q-F205
-F205
Instruction manual
Version: 2.04
286
© Arcteq Relays Ltd
IM00013