Settings
Table. 5.2.4 - 44. Settings of the frequency tracking.
Name
Range
Step
Default
Description
Sampling
mode
0: Fixed
1: Tracking
-
0: Fixed
Defines which measurement sampling mode is in use: the
fixed user-defined frequency, or the tracked system frequency.
System
nominal
frequency
7.000…75.000Hz 0.001Hz 50Hz
The user-defined system nominal frequency that is used when
the "Sampling mode" setting has been set to "Fixed".
Tracked
system
frequency
0.000…75.000Hz 0.001Hz -
Displays the rough measured system frequency.
Sampling
frequency in
use
0.000…75.000Hz 0.001Hz -
Displays the tracking frequency that is in use at that moment.
Frequency
reference 1
0: None
1: CT1IL1
2: CT2IL1
3: VT1U1
4: VT2U1
-
1: CT1IL1
The first reference source for frequency tracking.
Frequency
reference 2
0: None
1: CT1IL2
2: CT2IL2
3: VT1U2
4: VT2U2
-
1: CT1IL2
The second reference source for frequency tracking.
Frequency
reference 3
0: None
1: CT1IL3
2: CT2IL3
3: VT1U3
4: VT2U3
-
1: CT1IL3
The third reference source for frequency tracking.
Frequency
tracking
quality
0: No trackable
channels
1: Reference 1
trackable
2: Reference 2
trackable
3: References 1 &
2 trackable
4: Reference 3
trackable
5: Reference 1 &
3 trackable
6: References 2 &
3 trackable
7: All references
trackable
-
-
Defines the frequency tracker quality. If the measured current
(or voltage) amplitude is below the threshold, the channel
tracking quality is 0 and cannot be used for frequency tracking.
If all channels' magnitudes are below the threshold, there are
no trackable channels.
Frequency
measurement
in use
0: No track ch
1: Ref1
2: Ref2
3: Ref3
-
-
Indicates which reference is used at the moment for frequency
tracking.
Start behavior
0: Start tracking
immediately
1: First nominal or
tracked
-
0: Start
tracking
immediately
Defines the how the tracking starts. Tracking can start
immediately, or there can be a set delay time between the
receiving of the first trackable channel and the start of the
tracking.
Start sampling
with
0: Use track
frequency
1: Use nom
frequency
-
0: Use
track
frequency
Defines the start of the sampling. Sampling can begin with
a previously tracked frequency, or with a user-set nominal
frequency.
A
AQ
Q-F205
-F205
Instruction manual
Version: 2.04
88
© Arcteq Relays Ltd
IM00013
Содержание AQ F205
Страница 1: ...AQ F205 Feeder protection IED Instruction manual ...
Страница 2: ......
Страница 379: ...Figure 7 4 245 Example block scheme A AQ Q F205 F205 Instruction manual Version 2 04 Arcteq Relays Ltd IM00013 377 ...
Страница 389: ...Figure 8 7 254 Device installation A AQ Q F205 F205 Instruction manual Version 2 04 Arcteq Relays Ltd IM00013 387 ...