Table. 5.4.4 - 184. AR General settings.
Setting
Range
Step
Default SG
Description
Object for
AR
0: Object 1
1: Object 2
2: Object 3
3: Object 4
4: Object 5
-
0:
Object 1 8
Defines the monitored and/or controlled object, and the
monitoring and/or controlling signals issued. This selection can
be changed via the device's setting group selection in real
time.
AR Enabled
in SG
0: Disabled
1: Enabled
-
0:
Disabled 8
Enables and disables the auto-recloser in the current setting
group. Can be enabled and disabled in each setting group
independently. This selection can be changed via the device's
setting group selection in real time.
Require
manual
resetting
0: Required
1: Obj Close CMD
resets
-
0:
Required 8
Defines the auto-recloser resetting after locking (Final trip,
error condition). Resetting can be set to be only done
manually with a user defined signal, or it can be reset by a
general breaker "Close" command (from any source). This
selection can be changed via the device's setting group
selection in real time.
Successful
reclose
start general
reclaim
0: Only shot
reclaim
1: Shot reclaim
and general
reclaim
-
0: Only
shot
reclaim
8
Defines whether the auto-recloser runs after a successful
reclose (inc. shot reclaim time), or whether it enters the locked
state after a request for auto-reclosing is applied. If "Shot
reclaim and general reclaim" is selected, this selection defines
the minimum time allowed between auto-reclosing cycles
without changing the shot-specific reclaim times. This
selection can be changed via the device's setting group
selection in real time.
Lock-out
time
("Lockout
after
successful
AR")
0.000…1800.000s 0.005s 0.000s
8
Defines the lock-out time after a successful reclosing. When
set to 0.00 s, the recloser goes directly into the "Ready" state
after a successful reclosing. If this time is running while a new
reclosing request is applied, the auto-recloser opens the
breaker and enters the locked state to prevent further
reclosing attempts. This selection can be changed via the
device's setting group selection in real time.
Object close
reclaim time
0.000…1800.000s 0.005s 10.000s
8
Defines the "Close" reclaim time of the object. This time starts
when the object is manually closed or when the general
reclaim time is selected after a successful auto-reclosing. If an
auto-reclosing request is applied during this time, the auto-
recloser enters the locked state to prevent further reclosing
attempts. This selection can be changed via the device's
setting group selection in real time.
Table. 5.4.4 - 185. Auto-recloser shot settings.
Setting
Range
Step
Default
SG
Description
ARx Shot x
0: Disabled
1: Enabled
-
0:
Disabled 8
Enables/disables Shot x for request ARx. If "Disabled", the
ARx request skips Shot 1 and moves on to the next
enabled shot. If "Enabled", the ARx request executes
a shot according to Shot 1 settings. This selection can be
changed via the device's setting group selection in real
time.
ARx
Shot starting
delay
0.000…1800.000s 0.005s
0.000s
8
Defines the starting delay of the shot, i.e. the minimum
time an ARx request has to be active before openign the
breaker and entering the dead time delay counting. This
setting is used only when the ARx request comes from the
function's START signal. If the function's TRIP request
starting delay in not 0.000 s, the auto-recloser is
prevented from starting. Whenever the shot is not the first
one, this setting should be set to 0.000 s. This selection
can be changed via the setting group selection in real
time.
A
AQ
Q-F205
-F205
Instruction manual
Version: 2.04
© Arcteq Relays Ltd
IM00013
279
Содержание AQ F205
Страница 1: ...AQ F205 Feeder protection IED Instruction manual ...
Страница 2: ......
Страница 379: ...Figure 7 4 245 Example block scheme A AQ Q F205 F205 Instruction manual Version 2 04 Arcteq Relays Ltd IM00013 377 ...
Страница 389: ...Figure 8 7 254 Device installation A AQ Q F205 F205 Instruction manual Version 2 04 Arcteq Relays Ltd IM00013 387 ...