ime (10 s) is exceeded, and so the AR Running
AR Running, SSho
hot 2 Running
t 2 Running and
AR2 R
AR2 Request
equested
ed signals are terminated, and the AR R
AR Reclaim
eclaim calculation begins. The
difference between auto-reclosing and shot-specific reclaim times is that the function jumps
to the next available shot should the fault return. If a fault returns after a successful cycle and
the function's AR Reclaim signal is active, the function jumps directly to the Final Trip state
and then enters the lock-out state. The user can control this behavior through the function
settings. Both reclaim times can be set to 0 s when they are not needed, and the function
skips all timers that are set to zero.
11. The AR R
AR Reclaim
eclaim time is exceeded and the function is set to "Ready" to wait for the next
request.
Auto-recloser sequence from Trip with two shots (high-speed succeeds).
This auto-recloser scheme has the same starters and shots as the two previous examples. The setting
and signals are also the same. However, in this example the fault is cleared by the high-speed shot.
Figure. 5.4.4 - 184. Settings for I0dir> with two shots.
This type of sequence (i.e. the first shot clears the fault) represents 75...85 % of all faults that occur in
MV overhead line networks.
Figure. 5.4.4 - 185. Signal status graph of the transient earth fault auto-recloser cycle.
A
AQ
Q-F205
-F205
Instruction manual
Version: 2.04
© Arcteq Relays Ltd
IM00013
267
Содержание AQ F205
Страница 1: ...AQ F205 Feeder protection IED Instruction manual ...
Страница 2: ......
Страница 379: ...Figure 7 4 245 Example block scheme A AQ Q F205 F205 Instruction manual Version 2 04 Arcteq Relays Ltd IM00013 377 ...
Страница 389: ...Figure 8 7 254 Device installation A AQ Q F205 F205 Instruction manual Version 2 04 Arcteq Relays Ltd IM00013 387 ...