Figure. 5.4.4 - 187. Signal status graph of the permanent overcurrent auto-recloser cycle.
1. An overcurrent is found in the protected line causing the I> protection to pick up. This
activates the AR1 R
AR1 Request
equested
ed signal to begin to calculate the SSho
hot1 Star
t1 Start T
t Time
ime. This activates
the SSho
hot 1 Running
t 1 Running signal even though the auto-recloser function is not yet running.
2. The SSho
hot1 Star
t1 Start T
t Time
ime (500 ms) for has elapsed and the auto-recloser function starts running
(AR Running
AR Running). This sends an "Open" command to the breaker.
3. The circuit breaker is opened and the I> stage's START signal is released and simultaneously
REQ1 trip signal for auto-reclosing is released. The auto-recloser function starts calculating
the SSho
hot1 Dead T
t1 Dead Time
ime to close the breaker.
4. The SSho
hot1 Dead T
t1 Dead Time
ime (200 ms) is exceeded and the auto-recloser function sends a "Close"
request to the object breaker: the conditions are met and the breaker's "Close" command is
sent to the breaker's close coil.
5. The circuit breaker is closed and since fault was not cleared, a new pick-up of I> is detected.
A "Close" command is dropped after the breaker's "Closed" indication is received and the
auto-recloser function starts calculating the SSho
hot1 R
t1 Reclaim
eclaim TTime
ime simultaneously with the
SSho
hot1 Ar
t1 Arcing T
cing Time
ime.
6. The SSho
hot1 Ar
t1 Arcing T
cing Time
ime (200 ms) is exceeded which means that the fault is not cleared and
the function sends an "Open" command to the breaker. The function deactivates the SSho
hot1
t1
Running
Running signal and instead activates the SSho
hot2 Running
t2 Running signal.
7. The circuit breaker opens and the SSho
hot2 Dead T
t2 Dead Time
ime calculation begins.
8. The SSho
hot2 Dead T
t2 Dead Time
ime (120 s) is exceeded and the auto-recloser function sends a "Close"
command to the breaker.
9. The circuit breaker is closed towards the fault since it was not cleared by Shot 2. The I> stage
picks up and starts calculating the SSho
hot2 Ar
t2 Arcing T
cing Time
ime for the Final Trip. The "Close" command
is dropped after the the breaker's "Closed" indication is received. The auto-recloser function
also starts calculating the SSho
hot2 R
t2 Reclaim T
eclaim Time
ime.
10. The SSho
hot2 Ar
t2 Arcing T
cing Time
ime (200 ms) is exceeded and and the REQ1 request is given to the
function. However, as the function is in the process of calculating the SSho
hot2 R
t2 Reclaim T
eclaim Time
ime
when it receives this request, the function tries to move on to the next available shot. Alas,
this scheme does not have any more available shots and so the function begins the FFinal T
inal Trip
rip
state and drops the AR Running
AR Running, SSho
hot2 Running
t2 Running and AR1
AR1 R
Request
equested
ed signals. The function
enters the AR L
AR Lock-out
ock-out state to prevent any further requests for reclosing.
A
AQ
Q-F205
-F205
Instruction manual
Version: 2.04
© Arcteq Relays Ltd
IM00013
269