The user can set up to eight (8) magnitudes to be recorded when the function is triggered. An
overcurrent fault type, a voltage fault type, and a tripped stage can be recorded and reported straight
to SCADA.
NO
NOTE!
TE!
The available measurement values depend on the relay type. If only current analog
measurements are available, the recorder can solely use signals which only use current. The
same applies, if only voltage analog measurements are available.
Currents
Description
IL1 (ff), IL2 (ff), IL3 (ff), I01 (ff), I02
(ff)
The fundamental frequency current measurement values (RMS) of phase currents and
of residual currents.
IL1TRMS, IL2TRMS, IL3TRMS,
I01TRMS, I02TRMS
The TRMS current measurement values of phase currents and of residual currents.
IL1,2,3 & I01/I02 2
nd
h., 3
rd
h., 4
th
h., 5
th
h., 7
th
h., 9
th
h., 11
th
h., 13
th
h., 15
th
h., 17
th
h., 19
th
h.
The magnitudes of phase current components: Fundamental, 2
nd
harmonic, 3
rd
harmonic, 4
th
harmonic, 5
th
harmonic 7
th
, harmonic 9
th
, harmonic 11
th
, harmonic 13
th
,
harmonic 15
th
, harmonic 17
th
, harmonic 19
th
harmonic current.
I1, I2, I0Z
The positive sequence current, the negative sequence current and the zero sequence
current.
I0CalcMag
The residual current calculated from phase currents.
IL1Ang, IL2Ang, IL3Ang,
I01Ang, I02Ang, I0CalcAng,
I1Ang, I2Ang
The angles of each measured current.
VVolta
oltages
ges
Descrip
Description
tion
UL1Mag, UL2Mag, UL3Mag,
UL12Mag, UL23Mag, UL31Mag
U0Mag, U0CalcMag
The magnitudes of phase voltages, of phase-to-phase voltages, and of residual
voltages.
U1 Pos.seq V mag, U2 Neg.seq V
mag
The positive sequence voltage and the negative sequence voltage.
UL1Ang, UL2Ang, UL3Ang,
UL12Ang, UL23Ang, UL31Ang
U0Ang, U0CalcAng
The angles of phase voltages, of phase-to-phase voltages, and of residual voltages.
U1 Pos.seq V Ang, U2 Neg.seq V
Ang
The positive sequence angle and the negative sequence angle.
PPoow
wers
ers
Descrip
Description
tion
S3PH, P3PH, Q3PH
The three-phase apparent, active and reactive powers.
SL1, SL2, SL3, PL1, PL2, PL3,
QL1, QL2, QL3
The phase apparent, active and reactive powers.
tanfi3PH, tanfiL1, tanfiL2, tanfiL3
The tan (φ) of three-phase powers and phase powers.
cosfi3PH, cosfiL1, cosfiL2, cosfiL3
The cos (φ) of three-phase powers and phase powers.
Impedances and admit
Impedances and admittances
tances
Descrip
Description
tion
RL12, RL23, RL31
XL12, XL23, XL31,
RL1, RL2, RL3
XL1, XL2, XL3
Z12, Z23, Z31
ZL1, ZL2, ZL3
The phase-to-phase and phase-to-neutral resistances, reactances and impedances.
Z12Ang, Z23Ang, Z31Ang,
ZL1Ang, ZL2Ang, ZL3Ang
The phase-to-phase and phase-to-neutral impedance angles.
A
AQ
Q-F205
-F205
Instruction manual
Version: 2.04
356
© Arcteq Relays Ltd
IM00013
Содержание AQ F205
Страница 1: ...AQ F205 Feeder protection IED Instruction manual ...
Страница 2: ......
Страница 379: ...Figure 7 4 245 Example block scheme A AQ Q F205 F205 Instruction manual Version 2 04 Arcteq Relays Ltd IM00013 377 ...
Страница 389: ...Figure 8 7 254 Device installation A AQ Q F205 F205 Instruction manual Version 2 04 Arcteq Relays Ltd IM00013 387 ...