Figure. 5.4.5 - 197. Example of timers and pick-up parameters (no cold load pick-up, I
low
too short).
In the example above, the cold load pick-up function does not activate even when the measured
current dips below the
I
low
setting, because the
T
set
is not exceeded and therefore no cold load pick-up
signal is issued. If the user wants the function to activate within a shorter period of time, the
T
set
parameter can be se to a lower value. If the user wants no delay, the
T
set
can be zero seconds and the
operation will be immediate.
A
AQ
Q-F205
-F205
Instruction manual
Version: 2.04
© Arcteq Relays Ltd
IM00013
291