Device info
Figure. 4.3 - 5. Device info.
Table. 4.3 - 3. Parameters and indications in the
General menu.
Name
Range
Step
Default
Description
Device name
-
-
Unitname
The file name uses these fields when loading the .aqs
configuration file from the AQ-200 unit.
Device location
-
-
Unitlocation
Serial number
-
-
-
Displays the unit's unique serial number. The serial
number is also printed on the sticker located on the side
of the unit.
Firmware version
-
-
-
Displays the software version (firmware) used by the
unit. Upgradable by the user if a newer version is
available.
Hardware
configuration
-
-
-
Displays the hardware configuration of the unit. The
hardware configuration is also printed on the sticker
located on the side of the unit.
Time
synchronization source
0: Internal
1: External NTP
2: External Serial
3: IRIG-B
-
0: Internal
If an external clock time synchronization source is
available, the type is defined with this parameter. In
the internal mode there is no external Timesync source.
IRIG-B requires a serial fiber communication option
card.
Enable stage forcing
0: Disabled
1: Enabled
-
0: Disabled
When this parameter is enabled it is possible for the user
to force the protection, control and monitoring functions
to different statuses like START and TRIP. This is done in
the function’s
Info page with the Force status
to parameter.
System phase rotating
order
0: A-B-C
1: A-C-B
-
0: A-B-C
Allows the user to switch the expected order in which
the phase measurements are wired to the unit.
A
AQ
Q-F205
-F205
Instruction manual
Version: 2.04
16
© Arcteq Relays Ltd
IM00013