Figure. 5.4.1 - 173. Setting group control – two-wire connection from Petersen coil status with additional logic.
The images above depict a two-wire connection from the Petersen coil: the two images at the top
show a direct connection, while the two images on the bottom include additional logic. With a two-wire
connection the state of the Petersen coil can be monitored more securely. The additional logic ensures
that a single wire loss will not affect the correct setting group selection.
The application-controlled setting group change can also be applied entirely from the relay's internal
logics. For example, the setting group change can be based on the cold load pick-up function (see the
image below).
A
AQ
Q-F205
-F205
Instruction manual
Version: 2.04
246
© Arcteq Relays Ltd
IM00013
Содержание AQ F205
Страница 1: ...AQ F205 Feeder protection IED Instruction manual ...
Страница 2: ......
Страница 379: ...Figure 7 4 245 Example block scheme A AQ Q F205 F205 Instruction manual Version 2 04 Arcteq Relays Ltd IM00013 377 ...
Страница 389: ...Figure 8 7 254 Device installation A AQ Q F205 F205 Instruction manual Version 2 04 Arcteq Relays Ltd IM00013 387 ...