Setting
Range
Step
Default
Description
Use AR
On/Off
signals
0: Yes
1: No
-
1: No
Selects whether or not the AR ON and AR OFF signals are used. If set to "No"
the auto-recloser is always in use. If set to "Yes" binary signal set to "AR ON/
OFF" has to be active for the auto-recloser to be enabled.
AR
Status
0: AR is
inhibit
1: AR is ready
2: AR is
locked
3: AR is
running
4: AR is not
running
5: Lock out
delay is
running
6: Reclaim
time counting
7: Start time
counting
8: Dead time
counting
9: Arcing or
discr. time
counting
10: Reclaim
time counting
11: AR1
Requested
12: AR2
Requested
13: AR3
Requested
14: AR4
Requested
15: AR5
Requested
16: Executing
Shot1
17: Executing
Shot2
18: Executing
Shot3
19: Executing
Shot4
20: Executing
Shot5
21: Shot
Clear
-
-
When clicked open, displays the status of the function.
Timer
active
0: -
1: AR Lockout
2: AR Reset
Reclaim
3: AR Start
Delay
4: AR Dead
Time
5: AR
Discrimination
6: AR Shot
Reclaim
-
0: -
When the function is counting down towards any action, this parameter
displays what is the next expected action when the "AR Timer value" reaches
zero.
AR
Timer
value
0...1800.00s
0.005s 0s
When the function is counting down towards any action, this parameter
displays how much time is left until the action is executed. The "Timer active"
setting displays what is the action when this timer reaches zero.
A
AQ
Q-F205
-F205
Instruction manual
Version: 2.04
278
© Arcteq Relays Ltd
IM00013
Содержание AQ F205
Страница 1: ...AQ F205 Feeder protection IED Instruction manual ...
Страница 2: ......
Страница 379: ...Figure 7 4 245 Example block scheme A AQ Q F205 F205 Instruction manual Version 2 04 Arcteq Relays Ltd IM00013 377 ...
Страница 389: ...Figure 8 7 254 Device installation A AQ Q F205 F205 Instruction manual Version 2 04 Arcteq Relays Ltd IM00013 387 ...