Figure. 4.5 - 31. Digital input section.
All settings related to digital inputs can be found in the "Digital inputs" section.
The "Digital inputs settings" subsection includes various settings for the inputs: the polarity selection
determines whether the input is Normal Open (NO) or Normal Closed (NC) as well as the activation
threshold voltage (16…200 V AC/DC, step 0.1 V) and release threshold voltage (10…200 V AC/DC,
step 0.1 V) for each available input. There is also a setting to determine the wanted activation and
release delay (0…1800 s, step 1 ms). Digital input activation and release threshold follow the
measured peak value. The activation time of an input is 5…10 ms. The release time with DC is 5…10
ms, while with AC it is less than 25 ms. The first three digital inputs don't have activation and release
threshold voltage settings as these have already been defined when the unit was ordered.
Digital input statuses can be checked from the corresponding subsection ("Digital input status"). The
"Digital input descriptions" subsection displays the texts the user has written for each digital input. In
the "Event masks" subsection you can determine which events are masked –and therefore recorded
into the event history– and which are not.
Figure. 4.5 - 32. Digital outputs section.
All settings related to digital outputs can be found in the "Digital outputs" section.
A
AQ
Q-F205
-F205
Instruction manual
Version: 2.04
© Arcteq Relays Ltd
IM00013
35
Содержание AQ F205
Страница 1: ...AQ F205 Feeder protection IED Instruction manual ...
Страница 2: ......
Страница 379: ...Figure 7 4 245 Example block scheme A AQ Q F205 F205 Instruction manual Version 2 04 Arcteq Relays Ltd IM00013 377 ...
Страница 389: ...Figure 8 7 254 Device installation A AQ Q F205 F205 Instruction manual Version 2 04 Arcteq Relays Ltd IM00013 387 ...