Figure. 5.4.5 - 201. Example of timers and pick-up parameters (an inrush current detected during T
min
time).
In the example above, the cold load pick-up function activates after the measured current has stayed
below the
I
low
setting for a
T
set
amount of time. The current increases to between the
I
low
setting and
the
I
high
setting, which causes a counter to start counting towards the
T
min
time. Before the counter
reaches
T
min
, the current exceeds the
I
high
setting, which causes a counter to start counting towards
the
T
max
time. The cold load pick-up signal remains active until the
T
max
has been reached, or until the
start-up is over and the
Tmin
time is over.
Events and registers
The cold load pick-up function (abbreviated "CLP" in event block names) generates events and
registers from the status changes of the LowStart, HighStart, LoadNormal, Overcurrent,
CLPUActivated and BLOCKED signals of the cold load pick-up function as well as from the internal
pick-up comparators. The user can select which event messages are stored in the main event buffer:
ON, OFF, or both.
The events triggered by the function are recorded with a time stamp and with process data values.
Table. 5.4.5 - 192. Event codes.
Event number
Event channel
Event block name
Event code
Description
2688
42
CLP1
0
LowStart ON
2689
42
CLP1
1
LowStart OFF
2690
42
CLP1
2
HighStart ON
2691
42
CLP1
3
HighStart OFF
A
AQ
Q-F205
-F205
Instruction manual
Version: 2.04
© Arcteq Relays Ltd
IM00013
295
Содержание AQ F205
Страница 1: ...AQ F205 Feeder protection IED Instruction manual ...
Страница 2: ......
Страница 379: ...Figure 7 4 245 Example block scheme A AQ Q F205 F205 Instruction manual Version 2 04 Arcteq Relays Ltd IM00013 377 ...
Страница 389: ...Figure 8 7 254 Device installation A AQ Q F205 F205 Instruction manual Version 2 04 Arcteq Relays Ltd IM00013 387 ...