Figure. 4.4 - 8. Protection menu view.
Stage activation
You can activate the various protection stages in the
Stage activation submenu (see the images
below). Each protection stage and supporting function is disabled by default. When you activate one of
the stages, its activated menu appears in the stage-specific submenu. For example, the I>
(overcurrent) protection stage can be found in the "Current" module, whereas the U< (undervoltage)
protection stage can be found in the "Voltage" module.
Figure. 4.4 - 9. Submenus for Stage activation.
A
AQ
Q-F205
-F205
Instruction manual
Version: 2.04
© Arcteq Relays Ltd
IM00013