Name
Range
Description
Thermal
status
0: Light /
No load
1: High
overload
2:
Overloading
3: Load
normal
The function's thermal image status. When the measured current is below 1 % of the nominal
current, the status "Light/No load" is shown. When the measured current is below the trip limit,
the status "Load normal" is shown. When the measured current is above the pick-up limit but below
2 x
I
n
, the status "Overloading" is shown. When the measured current is above 2 x
I
n
, the status
"High overload" is shown.
TF>
Setting
alarm
0: SF
setting ok
1: Service
factor set
fault.
Override to
1.0
Indicates if SF setting has been set wrong and the actually used setting is 1.0. Visible only when
there is a setting fault.
TF>
Setting
alarm
0: Ambient
setting ok
1: Ambient
t set fault.
Override to
1.0
Indicates if ambient temperature settings have been set wrong and actually used setting is 1.0.
Visible only when there is a setting fault.
TF>
Setting
alarm
0: Nominal
current calc
ok
1: Nominal
current set
fault.
Override to
1.0
Indicates if nominal current calculation is set wrong and actually used setting is 1.0. Visible only
when there is a setting fault.
TF>
Setting
alarm
0: Ambient
setting ok
1:
Inconsistent
setting of
ambient k
Indicates if ambient k setting has been set wrong. Visible only when there is a setting fault.
Table. 5.3.19 - 161. Measurements.
Name
Range
Description/values
Currents
0: Primary A
1: Secondary A
2: Per unit
The active phase current measurement from IL1 (A), IL2 (B) and IL3 (C) phases in given
scalings.
Thermal
image
0: Thermal image
calc.
- TF> Trip expect mode: No trip expected/Trip expected
- TF> Time to 100 % theta: Time to reach the 100 % thermal cap
- TF> Rreference T curr.: reference/pick-up value (IEQ)
- TF> Active meas. curr.: the measured maximum TRMS current at a given moment
- TF> T est. with act. curr.: estimation of the used thermal capacity including the current at
a given moment
- TF> T at a given moment: the thermal capacity used at that moment
1: Temp. estimates
- TF> Used k for amb. temp: the ambient correction factor at a givenmoment
- TF> Max. temp. rise all.: the maximum allowed temperature rise
- TF> Temp. rise atm: the calculated temperature rise at a given moment
- TF> Hot spot estimate: the estimated hot spot temperature including the ambient
temperature
- TF> Hot spot max. all.: the maximum allowed temperature for the object
A
AQ
Q-F205
-F205
Instruction manual
Version: 2.04
© Arcteq Relays Ltd
IM00013
235
Содержание AQ F205
Страница 1: ...AQ F205 Feeder protection IED Instruction manual ...
Страница 2: ......
Страница 379: ...Figure 7 4 245 Example block scheme A AQ Q F205 F205 Instruction manual Version 2 04 Arcteq Relays Ltd IM00013 377 ...
Страница 389: ...Figure 8 7 254 Device installation A AQ Q F205 F205 Instruction manual Version 2 04 Arcteq Relays Ltd IM00013 387 ...