Name
Range
Step
Description
Import Active Energy (kWh or MWh)
-1x10
9
…1x10
9
0.01
The imported active energy of the phase.
Active Energy (P) Export/Import
balance (kWh or MWh)
-1x10
9
…1x10
9
0.01
The sum of the phase's imported and exported active
energy.
Exported (Q) while Export (P) Lx (kVarh
or MVarh)
-1x10
9
…1x10
9
0.01
The exported reactive energy of the phase while active
energy is exported.
Imported (Q) while Export (P) Lx (kVarh
or MVarh)
-1x10
9
…1x10
9
0.01
The imported reactive energy of the phase while active
energy is exported.
Reactive Energy (Q) balance while
Export (P) Lx (kVarh or MVarh)
-1x10
9
…1x10
9
0.01
The sum of the phase's imported and exported
reactive energy while active energy is exported.
Exported (Q) while Import (P) Lx (kVarh
or MVarh)
-1x10
9
…1x10
9
0.01
The exported reactive energy of the phase while active
energy is imported.
Imported (Q) while Import (P) Lx (kVarh
or MVarh)
-1x10
9
…1x10
9
0.01
The imported reactive energy of the phase while active
energy is imported.
Reactive energy (Q) balance while
Import (P) Lx (kVarh or MVarh)
-1x10
9
…1x10
9
0.01
The sum of the phase's imported and exported reactive
energy while active energy is imported.
Apparent Energy (S) while Export (P) Lx -1x10
9
…1x10
9
0.01
The apparent energy of the phase while active energy is
exported.
Apparent Energy (S) while Import (P) Lx -1x10
9
…1x10
9
0.01
The apparent energy of the phase while active energy is
imported.
Calculation examples
Here is an example of power calculation. Both wiring methods (line-to-line and line-to-neutral) are
checked with the same signal injection. The voltage scaling is set to 20 000 : 100 V and the current
scaling is set to 1000 : 5 A.
Voltages (line-to-neutral):
Currents:
U
L1
= 40.825 V, 45.00°
I
L1
= 2.5 A, 0.00°
U
L2
= 61.481 V, -159.90°
I
L2
= 2.5 A, -120.00°
U
L3
= 97.742 V, 126.21°
I
L3
= 2.5 A, 120.00°
A
AQ
Q-F205
-F205
Instruction manual
Version: 2.04