background image

SAVE THESE INSTRUCTIONS

THIS PRODUCT CONTAINS A RECHARGEABLE LITHIUM-ION BATTERY.  

THE BATTERY MUST BE RECYCLED OR DISPOSED OF PROPERLY.

 Bodine © 2018 Signify Holding. All rights reserved.  

236 Mt. Pleasant Rd. • Collierville, TN USA 38017-2752 • Tech Support 888-263-4638 • Fax 901-853-5009 • www.bodine.com 

442294606602

BSL10LST

02/07/19

Li - ion

CLASS 2 OUTPUT

Self-Testing Emergency LED Driver

READ AND FOLLOW ALL SAFETY INSTRUCTIONS

! IMPORTANT SAFEGUARDS !

WHEN USING ELECTRICAL EQUIPMENT, BASIC

SAFETY PRECAUTIONS SHOULD ALWAYS BE 

FOLLOWED, INCLUDING THE FOLLOWING:

  1.  To prevent voltage from being present on output leads prior to installation, unit engage connector must be  
    open. Do not join unit engage connector until installation is complete and AC power is supplied to the  
    emergency driver.
  2.  This product is for use with an emergency LED lighting load and supplies nominaly 10.0 W of power, with 
    a voltage of 15-54 VDC in emergency mode for a minimum of 90 minutes, in compliance with NFPA-101 and    
    NEC 700.12.  
  3.  Make sure all connections are in accordance with the National Electrical Code or Canadian Electrical Code and   
    any local regulations.
  4.  To reduce the risk of electric shock, disconnect both normal and emergency power supplies and unit engage   
    connector of the emergency driver before servicing.
 5. This emergency driver is intended to be mounted and enclosed within a luminaire and is suitable for both  
    factory or field installation. For field installation, please see the instructions on page 2. 
  6.  This product is suitable for use in damp locations where the ambient temperature is 0ºC minimum, +55ºC  
    maximum. Product is also suitable for installation in sealed and gasketed fixtures. Product is not suitable  

 

    for heated air outlets and wet or hazardous locations. Maximum allowable case temp is 63ºC. See Page 4  
    for Tcase measurement location.
  7.  An unswitched AC power source is required (120-277 VAC, 50/60 Hz).
  8.  Do not install near gas or electric heaters.
  9.  Do not attempt to service the battery. A sealed, no-maintenance battery is used that is not field replaceable.   
    Contact the manufacturer for information on service.
 10.  The use of accessory equipment not recommended by the manufacturer may cause an unsafe condition.
 11.  Do not use this product for other than intended use.
 12.  Servicing should be performed by qualified service personnel.
 13.  Equipment should be mounted in locations and at heights where it will not be subjected to tampering by  

 

    unauthorized personnel.
 14.  For Canadian application the output terminals should be in compliance with the accessibility requirement of  
    the Canadian Electric Code.
15.   This device complies with part 15 of the FCC Rules. Operation is subject to the following two conditions: (1) 
    this device may not cause harmful interference, and (2) this device must accept any interference that may    
    cause undesired operation.
16.  This product must be grounded. See the wiring diagrams for details.

Installation Instructions

Содержание BSL10LST

Страница 1: ...minaire and is suitable for both factory or field installation For field installation please see the instructions on page 2 6 This product is suitable for use in damp locations where the ambient temperature is 0ºC minimum 55ºC maximum Product is also suitable for installation in sealed and gasketed fixtures Product is not suitable for heated air outlets and wet or hazardous locations Maximum allow...

Страница 2: ...ings in the luminaire specifications or imprinted directly on the LED arrays If multiple LED arrays are to be driven verify that the total forward voltage is within the limits of this product Using a voltage meter it may be possible to directly measure the voltage across the LED arrays when operating from the AC driver 3 Ensure the output current of the AC LED driver does not exceed 5 0 Amps This ...

Страница 3: ...e pre punched by the luminaire supplier Wire the test switch per wiring diagrams provided on these instructions If wired correctly the 2W ITS indicator light should be ON when AC power is supplied to the fixture and the convertor connector is closed indicating that the emergency inverter battery is charging After installing mark with the PUSH TO TEST and CHARGING INDICATOR LIGHT labels Hex Nut 2 W...

Страница 4: ... DRIVER WALL SWITCH UNSWITCHED HOT WHITE LED BLACK GRAY BLUE BLACK RED BLACK LED GREEN NEUTRAL GROUND WHITE GRAY GROUND NEUTRAL LINE GRAY LED LOAD L E D D R I V E R E M E R G E N C Y UNIT ENGAGE GRAY VIOLET VIOLET BROWN BROWN 2W ITS 0 59 15 mm Tc 212 mm 8 03 MAINTENANCE This self testing emergency driver automatically performs required routine testing Results are reported to maintenance personnel ...

Отзывы: