![ABB 650 series Скачать руководство пользователя страница 91](http://html.mh-extra.com/html/abb/650-series/650-series_technical-manual_2503091.webp)
Section 6
Differential protection
6.1
Transformer differential protection
6.1.1
Functionality
Transformer differential protection, three-winding T3WPDIF (87T) is provided with
internal CT ratio matching and phase shift compensation. In addition, zero sequence
elimination is also provided.
The function can be provided with -phase sets of current inputs. All current inputs are
provided with percentage bias restraint features, making the IED suitable for two- or
three-winding transformer arrangements.
Three-winding applications
xx05000052_ansi.vsd
352
152
452
ANSI05000052 V1 EN
xx05000049_ansi.vsd
152
352
ANSI05000049 V1 EN
Figure 29:
CT group arrangement
for differential
protection and other
protections
The available settings of this function allow the REG650 to cover various differential
protection applications such as power transformers and auto-transformers with or without
1MRK 502 048-UUS A
Section 6
Differential protection
85
Technical manual