8.1.9
Technical data
Table 89:
OC4PTOC (51/67) technical data
Function
Setting range
Accuracy
Operate current
(5-2500)% of
lBase
±
1.0% of I
n
at I ≤ I
n
±
1.0% of I at I > I
n
Reset ratio
> 95% at (50–2500)% of
lBase
-
Min. operating current
(5-10000)% of
lBase
±
1.0% of I
n
at I ≤ I
n
±
1.0% of I at I > I
n
2nd harmonic blocking
(5–100)% of fundamental
±
2.0% of I
n
Independent time delay
(0.000-60.000) s
±
0.5%
±
25 ms
Minimum operate time for
inverse characteristics
(0.000-60.000) s
±
0.5%
±
25 ms
Inverse characteristics, see
and table
15 curve types
1)
ANSI/IEEE C37.112
IEC 60255–151
±
3% or
±
40 ms
0.10 ≤ k ≤ 3.00
1.5 x I
set
≤ I ≤ 20 x I
set
Operate time, nondirectional
pickup function
25 ms typically at 0 to 2 x I
set
-
Reset time, pickup function
35 ms typically at 2 to 0 x I
set
-
Operate time, directional pickup
function
50 ms typically at 0 to 2 x I
set
-
Reset time, directional pickup
function
35 ms typically at 2 to 0 x I
set
-
Critical impulse time
10 ms typically at 0 to 2 x I
set
-
Impulse margin time
15 ms typically
-
1)
Note: Timing accuracy only valid when 2nd harmonic blocking is turned off
8.2
Four step residual overcurrent protection, zero,
negative sequence direction EF4PTOC (51N/67N)
8.2.1
Identification
Function description
IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Four step residual overcurrent
protection, zero or negative sequence
direction
EF4PTOC
2
IEC11000263 V1 EN
51N/67N
1MRK 502 048-UUS A
Section 8
Current protection
203
Technical manual
Содержание 650 series
Страница 1: ...Relion 650 series Generator protection REG650 ANSI Technical manual ...
Страница 2: ......
Страница 44: ...38 ...
Страница 62: ...56 ...
Страница 68: ...62 ...
Страница 156: ...150 ...
Страница 198: ...192 ...
Страница 512: ...506 ...
Страница 644: ...638 ...
Страница 714: ...708 ...
Страница 777: ...771 ...