block. A parameter in function block LOCREM is set to choose if the switch signals are
coming from the local HMI or from an external hardware switch connected via binary
inputs.
12.2.6.3
Function block
LOCREM
CTRLOFF
LOCCTRL
REMCTRL
LHMICTRL
OFF
LOCAL
REMOTE
VALID
IEC09000076_1_en.vsd
IEC09000076 V1 EN
Figure 171:
LOCREM function block
12.2.6.4
Signals
Table 226:
LOCREM Input signals
Name
Type
Default
Description
CTRLOFF
BOOLEAN
0
Disable control
LOCCTRL
BOOLEAN
0
Local in control
REMCTRL
BOOLEAN
0
Remote in control
LHMICTRL
INTEGER
0
LHMI control
Table 227:
LOCREM Output signals
Name
Type
Description
OFF
BOOLEAN
Control is disabled
LOCAL
BOOLEAN
Local control is activated
REMOTE
BOOLEAN
Remote control is activated
VALID
BOOLEAN
Outputs are valid
12.2.6.5
Settings
Table 228:
LOCREM Non group settings (basic)
Name
Values (Range)
Unit
Step
Default
Description
ControlMode
Internal LR-switch
External LR-switch
-
-
Internal LR-switch
Control mode for internal/external LR-switch
1MRK 502 048-UUS A
Section 12
Control
369
Technical manual