Signals
Table 317:
AND Input signals
Name
Type
Default
Description
INPUT1
BOOLEAN
1
Input signal 1
INPUT2
BOOLEAN
1
Input signal 2
INPUT3
BOOLEAN
1
Input signal 3
INPUT4
BOOLEAN
1
Input signal 4
Table 318:
AND Output signals
Name
Type
Description
OUT
BOOLEAN
Output signal
NOUT
BOOLEAN
Inverted output signal
Settings
The function does not have any parameters available in Local HMI or Protection and
Control IED Manager (PCM600).
13.3.1.10
Set-reset memory function block SRMEMORY
Identification
Function description
IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Set-reset memory function block
SRMEMORY
-
-
Functionality
The Set-Reset function SRMEMORY is a flip-flop with memory that can set or reset an
output from two inputs respectively. Each SRMEMORY function block has two outputs,
where one is inverted. The memory setting controls if the flip-flop after a power
interruption will return the state it had before or if it will be reset. For a Set-Reset flip-flop,
SET input has higher priority over RESET input.
Table 319:
Truth table for the Set-Reset (SRMEMORY) function block
SET
RESET
OUT
NOUT
1
0
1
0
0
1
0
1
1
1
1
0
0
0
0
1
Section 13
1MRK 502 048-UUS A
Logic
484
Technical manual
Содержание 650 series
Страница 1: ...Relion 650 series Generator protection REG650 ANSI Technical manual ...
Страница 2: ......
Страница 44: ...38 ...
Страница 62: ...56 ...
Страница 68: ...62 ...
Страница 156: ...150 ...
Страница 198: ...192 ...
Страница 512: ...506 ...
Страница 644: ...638 ...
Страница 714: ...708 ...
Страница 777: ...771 ...